Learning Advanced Features
72
TI Pulse Input Setting Details
Code
Description
In.69 P5 Define
For Standard I/O, Pulse input TI and Multi-function terminal P5 share the same
terminal. Set the In.69 (P5 Define) to 54(TI).
In.01 Freq at 100%
Configures the frequency reference at the maximum pulse input. The
frequency reference is based on 100% of the value set with In.96.
•
If In.01 is set to 60.00 and codes In.93–96 are set at default, 32kHz input to
TI yields a frequency reference of 60.00Hz.
•
If In.96 is set to 50.00 and codes In.01, In.93–95 are set at default, 32kHz
input to the TI terminal yields a frequency reference of 30.00Hz.
In.91 Pulse Monitor Displays the pulse frequency supplied at TI.
In.92 TI Filter
Sets the time for the pulse input at TI to reach 63% of its nominal frequency
(when the pulse frequency is supplied in multiple steps).
In.93 TI Pls x1
In.94 TI Perc y1
In.95 TI Pls x2
In.96 TI Perc y2
Configures the gradient level and offset values for the output frequency.
[In.93 TI Pls x1 (min. pulse freq.), In.94 TI Perc y1 (min. % speed)]
In.95 TI Pls x2 (max. pulse freq.), In.96 TI Perc y2 (max. % speed)]
In.97 TI Inverting–
In.98 TI Quantizing
Identical to In.16
–
17 (refer to In.16 V1 Inverting/In.17.V1 Quantizing on page
65
).
In.96
In.94
In.93
In.95
TI
Frequency reference
input
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......