Learning Advanced Features
125
Jog operation
There are three different ways to put the inverter in the jog mode.
•
Jog-1 using a digital input terminal set to JOG along with a run command (Fx or Rx).
•
Jog-2 using only a single digital input set to FWD JOG or REV JOG.
•
using the [ESC] key on the keypad (see also programming of the ESC key, Section 4.6).
The jog operation overrides all other operation modes, except the dwell operation. The jog
operation is the second highest priority operation. If a jog operation is requested while operating
the multi-step, up-down, or 3-wire operation modes, the jog operation takes precedence.
Jog Operation 1-Forward Jog by Multi-function Terminal
The jog operation is available in either forward or reverse direction using the digital input
terminals. The table below lists parameter setting for a forward jog operation.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
dr
11
Jog frequency JOG
Frequency
10.00
0.50-Maximum
frequency
Hz
12
Jog operation
acceleration
time
JOG Acc Time 20.00
0.00-600.00
sec
13
Jog operation
deceleration
time
JOG Dec Time 30.00
0.00-600.00
sec
In
65-69
Px terminal
configuration
Px Define(Px:
P1–P5)
6
JOG
-
-
OP
Drv
Px terminal
configuration
Px Define(Px:
P1–P5)
1
Fx/Rx-1
-
-
Forward Jog Description Details
Code
Description
In.65–71 Px Define
Select a digital input from P1- P5 and program to 6. Jog from In.65-69.
[Terminal settings for jog operation]
dr.11 JOG Frequency
Set the operation frequency.
dr.12 JOG Acc Time
Set the acceleration speed.
P1
P5
CM
1(FX)
6(JOG)
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......