269
Table of Functions
Code
Comm.
Address
Name
LCD Display
Setting Range
Initial
Value
Property* V/F SL Ref.
power on
Run
1
Yes
12
17
0h130C
DC braking time
at startup
DC-Start
Time
0.00-60.00(s)
0.00
X/A
O
I/P
p.96
13
0h130D
Amount of
applied DC
DC Inj Level
0-200(%)
50
X/A
O
I/P
p.96
14
18
0h130E
Output blocking
time before DC
braking
DC-Block
Time
0.00- 60.00(s)
0.10
X/A
O
I/P
p.97
15
18
0h130F DC braking time
DC-Brake
Time
0.00- 60.00(s)
1.00
X/A
O
I/P
p.97
16
18
0h1310 DC braking rate
DC-Brake
Level
0-200(%)
50
X/A
O
I/P
p.97
17
18
0h1311
DC braking
frequency
DC-Brake
Freq
Start frequency-
60Hz
5.00
X/A
O
I/P
p.97
20
0h1314
Dwell frequency
on acceleration
Acc Dwell
Freq
Start frequency-
Maximum
frequency(Hz)
5.00
X/A
O
I/P
p.132
21
0h1315
Dwell operation
time on
acceleration
Acc Dwell
Time
0.0-60.0(s)
0.0
X/A
O
I/P
p.132
22
0h1316
Dwell frequency
on deceleration
Dec Dwell
Freq
Start frequency-
Maximum
frequency(Hz)
5.00
X/A
O
I/P
p.132
23
0h1317
Dwell operation
time on
deceleration
Dec Dwell
Time
0.0-60.0(s)
0.0
X/A
O
I/P
p.132
24
0h1318 Frequency limit Freq Limit
0
No
0:No
X/A
O
I/P
p.100
1
Yes
25
19
0h1319
Frequency lower
limit value
Freq Limit Lo
0.00-Upper limit
frequency(Hz)
0.50
O/A
O
I/P
p.100
26
19
0h131A
Frequency
upper limit value
Freq Limit Hi
Lower limit
frequency-
Maximum
frequency(Hz)
maxim
um
frequen
cy
X/A
O
I/P
p.100
27
0h131B Frequency jump Jump Freq
0
No
0:No
X/A
O
I/P
p.101
1
Yes
17
Displayed when Ad. 07 is set to 1 (DC-Start).
18
Displayed when Ad. 08 is set to 1 (DC-Brake).
19
Displayed when Ad. 24 is set to 1 (Yes).
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......