Learning Advanced Features
148
Group Code
Name
LCD Display
Parameter Setting
Setting
Range
Unit
setting
54
Forward
direction
retrograde
torque limit
FWD +Trq Lmt
180.0
0.0-200.0 %
55
Forward
direction
regenerative
torque limit
FWD -Trq Lmt
180.0
0.0-200.0 %
56
Reverse
direction
retrograde
torque limit
REV +Trq Lmt
180.0
0.0-200.0 %
57
Reverse
direction
regenerative
torque limit
REV -Trq Lmt
180.0
0.0-200.0 %
85*
Flux estimator
proportional
gain 1
Flux P Gain1
370
100-700
-
86*
Flux estimator
proportional
gain 2
Flux P Gain2
0
0-100
-
87*
Flux estimator
proportional
gain 3
Flux P Gain3
100
0-500
-
88*
Flux estimator
integral gain 1
Flux I Gain1
50
0-200
-
89*
Flux estimator
integral gain2
Flux I Gain2
50
0-200
-
90*
Flux estimator
integral gain 3
Flux I Gain3
50
0-200
-
91*
Sensorless
voltage
compensation
1
SL Volt Comp1
30
0-60
-
92*
Sensorless
voltage
compensation
2
SL Volt Comp2
20
0-60
-
93*
Sensorless
voltage
compensation
SL Volt Comp3
20
0-60
-
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......