4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G120D
908
List Manual (LH14), 01/2016, A5E33842313
Note:
IF: interface
Remedy:
Map fewer process data in PDO.
Apply one of the following options to delete the alarm:
- POWER ON (switch-off/switch-on).
- carry out a warm restart (p0009 = 30, p0976 = 2).
- execute CANopen NMT command reset node.
- change CANopen NMT state.
- delete alarm buffer [0...7] (p2111 = 0).
A08800
PROFIenergy energy-saving mode active
Message class:
Communication error to the higher-level control system (9)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The PROFIenergy energy-saving mode is active
Alarm value (r2124, interpret decimal):
Mode ID of the active PROFIenergy energy-saving mode.
See also: r5600 (Pe energy-saving mode ID)
Remedy:
The alarm is automatically withdrawn when the energy-saving mode is exited.
Note:
The energy-saving mode is exited after the following events:
- the PROFIenergy command end_pause is received from the higher-level control.
- the higher-level control has changed into the STOP operating state.
- the PROFINET connection to the higher-level control has been disconnected.
A08802
PROFIenergy not possible to switch off incremental encoder supply
Message class:
Communication error to the higher-level control system (9)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The incremental encoder is used for the closed-loop position control. This means that its power supply cannot be
switched off during the PROFIenergy energy-saving mode, otherwise it would lose its position actual value.
Alarm value (r2124, interpret decimal):
Encoder number
Remedy:
The alarm is automatically withdrawn when the energy-saving mode is exited.
Note:
The energy-saving mode is exited after the following events:
- the PROFIenergy command end_pause is received from the higher-level control.
- the higher-level control has changed into the STOP operating state.
- the PROFINET connection to the higher-level control has been disconnected.
F13009
Licensing OA application not licensed
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
At least one OA application which is under license does not have a license.
Note:
Refer to r4955 and p4955 for information about the installed OA applications.
Remedy:
- enter and activate the license key for OA applications under license (p9920, p9921).
- if necessary, de-activate unlicensed OA applications (p4956).
F13100
Know-how protection: Copy protection error
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF1
Acknowledge:
IMMEDIATELY
Cause:
The know-how protection with copy protection for the memory card is active.
An error has occurred when checking the memory card.