4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G120D
934
List Manual (LH14), 01/2016, A5E33842313
C30798
SI Motion P2: Test stop for motion monitoring functions running
Message class:
Safety monitoring channel has identified an error (10)
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The forced checking procedure (test stop) for the safe motion monitoring functions is currently in progress.
Remedy:
Not necessary.
The message is automatically withdrawn when the test stop has been completed.
Note:
SI: Safety Integrated
C30799
SI Motion P2: Acceptance test mode active
Message class:
Safety monitoring channel has identified an error (10)
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The acceptance test mode is active.
Remedy:
Not necessary.
The message is withdrawn when exiting the acceptance test mode.
N30800 (F)
Power unit: Group signal
Message class:
Power electronics faulted (5)
Reaction:
OFF2
Acknowledge:
NONE
Cause:
The power unit has detected at least one fault.
Remedy:
Evaluate the other messages that are presently available.
F30802
Power unit: Time slice overflow
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A time slice overflow has occurred.
Fault value (r0949, interpret decimal):
xx: Time slice number xx
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
F30804 (N, A)
Power unit: CRC
Message class:
Hardware/software error (1)
Reaction:
OFF2 (OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
A checksum error (CRC error) has occurred for the power unit.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
F30805
Power unit: EEPROM checksum error
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Internal parameter data is corrupted.
Fault value (r0949, interpret hexadecimal):
01: EEPROM access error.
02: Too many blocks in the EEPROM.
Remedy:
Replace the module.