SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
131
2 Parameters
2.2 List of parameters
Description:
Displays what has the master control.
The drive can be controlled via the BICO interconnection or from external (e.g. the commissioning software).
Dependency:
Refer to: p0806
Notice:
The master control only influences control word 1 and speed setpoint 1. Other control word/setpoints can be
transferred from another automation device.
Note:
Bit 0 = 0: BICO interconnection active
Bit 0 = 1: Master control for PC/AOP
The commissioning software (drive control panel) uses the master control, for example.
Description:
Copies one Command Data Set (CDS) into another.
Index:
[0] = Source Command Data Set
[1] = Target Command Data Set
[2] = Start copying procedure
Dependency:
Refer to: r3996
Notice:
When the command data sets are copied, short-term communication interruptions may occur.
Note:
Procedure:
1. In Index 0, enter which command data set should be copied.
2. In index 1, enter the command data set that is to be copied into.
3. Start copying: set index 2 from 0 to 1.
p0809[2] is automatically set to 0 when copying is completed.
Description:
Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency:
Refer to: r0050, p0811, r0836
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
r0807.0
BO: Master control active / PcCtrl active
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Master control active
Yes
No
3030,
6031
p0809[0...2]
Copy Command Data Set CDS / Copy CDS
Access level:
2
Calculated:
-
Data type:
Unsigned8
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8560
Min Max
Factory
setting
0 3 0
p0810
BI: Command data set selection CDS bit 0 / CDS select., bit 0
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8560
Min Max
Factory
setting
- - 722.3