2 Parameters
2.2 List of parameters
SINAMICS G120D
386
List Manual (LH14), 01/2016, A5E33842313
For bit 09:
When evaluating the encoder signals (track signals, zero marks, absolute values, ...) an illegal signal state was
detected. Check the encoder / state of the encoder signals. Observe the maximum frequencies.
For bit 10:
The internal communication between the SINAMICS components is faulted or interrupted. Check the DRIVE-CLiQ
wiring. Ensure an EMC-compliant design. Observe the maximum permissible quantity structure / clock cycles.
For bit 11:
The infeed is faulted or has failed. Check the infeed and the surroundings (line supply, filter, reactors, fuses, ...).
Check the closed-loop infeed control.
For bit 15:
Group fault. Determine the precise cause of the fault using the commissioning tool.
Description:
Sets the re-parameterization of all safety messages for faults and alarms.
The relevant message type during changeover is selected by the firmware.
0: Safety messages are not re-parameterized
1: Safety messages are re-parameterized
Note:
A change only becomes effective after a POWER ON.
Description:
Displays the component of the fault which has occurred.
Value:
0:
No assignment
1:
Control Unit
2:
Power Module
3:
Motor
4:
Encoder evaluation (X6)
5:
Encoder at X6
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109, r2130, r2133, r2136, r3122
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
Description:
Displays the component of the fault which has occurred.
Value:
0:
No assignment
1:
Control Unit
2:
Power Module
3:
Motor
4:
Encoder evaluation (X6)
5:
Encoder at X6
6:
Encoder evaluation (X10)
7:
Encoder at X10
p3117
Change safety message type / Ch. SI mess type
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 1 0
r3120[0...63]
Component fault / Comp fault
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8060
Min Max
Factory
setting
0 5 -
r3120[0...63]
Component fault / Comp fault
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
8060
Min Max
Factory
setting
0 7 -