2 Parameters
2.2 List of parameters
SINAMICS G120D
250
List Manual (LH14), 01/2016, A5E33842313
Value:
0:
Automatic changeover SVM/FLB
2:
Space vector modulation (SVM)
3:
SVM without overcontrol
4:
SVM/FLB without overcontrol
Dependency:
If a sine-wave filter is parameterized as output filter (p0230 = 3, 4), then only space vector modulation without
overcontrol can be selected as modulation type (p1802 = 3).
Refer to: p0230, p0500
Note:
When modulation modes are enabled that could lead to overmodulation (p1802 = 0, 2), the modulation depth must be
limited using p1803 (default p1803 < 100 %). The higher the overmodulation, the greater the current ripple and
torque ripple.
When changing p1802[x], the values for all of the other existing indices are also changed.
Description:
Defines the maximum modulation depth.
Dependency:
Default setting PM260: 103 %.
Refer to: p0500
Note:
p1803 = 100% is the overcontrol limit for space vector modulation (for an ideal drive converter without any switching
delay).
Description:
Sets the filter time constant for the DC link voltage.
This time constant is used to calculate the modulation depth.
Description:
DC link voltage used to determine the maximum possible output voltage.
Description:
Displays the effective modulator mode.
Value:
1:
Flat top modulation (FLB)
2:
Space vector modulation (SVM)
9:
Optimized pulse pattern
p1803[0...n]
Maximum modulation depth / Modulat depth max
Access level:
3
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6723
Min Max
Factory
setting
20.0 [%]
150.0 [%]
106.0 [%]
p1806[0...n]
Filter time constant Vdc correction / T_filt Vdc_corr
Access level:
4
Calculated:
p0340 = 1,3
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.0 [ms]
10000.0 [ms]
0.0 [ms]
r1808
DC link voltage actual value for U_max calculation / Vdc act val U_max
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2001
Dyn. index:
-
Unit group:
5_2
Unit selection:
p0505
Func. diagram:
-
Min Max
Factory
setting
- [V]
- [V]
- [V]
r1809
CO: Modulator mode actual / Modulator mode act
Access level:
4
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
1 9 -