SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
59
2 Parameters
2.2 List of parameters
Notice:
If a catalog motor is selected (p0300 >= 100) and an associated motor code number (p0301), then the parameters
that are associated with this list cannot be changed (write protection). The write protection is canceled if the motor
type p0300 is set to a non-Siemens motor that matches p0301 (e.g. p0300 = 1 for p0301 = 1xxxx). Write protection is
automatically canceled when the results of motor data identification are copied to the motor parameters.
The motor type of a catalog motor corresponds to the upper three digits of the code number or the following
assignment (if the particular motor type is listed):
Type/code number ranges
100 / 100xx, 110xx, 120xx, 130xx, 140xx, 150xx
271 / 271xx, 281xx
277 / 277xx, 287xx, 297xx
Note:
With p0300 = 10000, for a motor with DRIVE-CLiQ, the motor parameters are automatically downloaded, with p0300
= 10001, the motor parameters of a second data set (if available).
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
A motor type with a value above p0300 >= 100 describes motors for which a motor parameter list exists.
Motor types with a value below p0300 < 100 correspond to the selection of a third-party motor. When appropriately
selected, this means that the motor parameters are pre-assigned the settings for a third-party motor.
This also applies for parameters for a motor with DRIVE-CLiQ. In this case p0300 can only be set to p0300 = 10000
or 10001 (read motor parameters) or to the corresponding non-Siemens motor (first digit of the motor code number)
in order to be able to cancel the write protection.
Description:
The parameter is used to select a motor from a motor parameter list.
When changing the code number (with the exception to the value 0), all of the motor parameters are pre-assigned
from the internally available parameter lists.
Dependency:
Code numbers can only be selected for motor types that correspond to the motor type selected in p0300.
Refer to: p0300
Note:
The motor code number can only be changed if the matching catalog motor was first selected in p0300.
When selecting a catalog motor (p0300 >= 100), drive commissioning can only be exited if a code number is
selected.
If a change is made to a non-catalog motor, then the motor code number should be reset (p0301 = 0).
Description:
Sets the rated motor voltage (rating plate).
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
Once the Control Unit has booted for the first time or if the factory settings have been restored, the parameter is pre-
assigned to match the power unit.
Description:
Sets the rated motor current (rating plate).
p0301[0...n]
Motor code number selection / Mot code No. sel
Access level:
2
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(1, 3)
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 65535
0
p0304[0...n]
Rated motor voltage / Mot U_rated
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(1, 3)
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
6301, 6724
Min Max
Factory
setting
0 [Vrms]
20000 [Vrms]
0 [Vrms]
p0305[0...n]
Rated motor current / Mot I_rated
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(1, 3)
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
6301
Min Max
Factory
setting
0.00 [Arms]
10000.00 [Arms]
0.00 [Arms]