SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
497
2 Parameters
2.2 List of parameters
Description:
Setting parameter for the run sequence of instance AND 2 within the run-time group set in p20040.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description:
Sets the signal source of input quantities I0, I1, I2, I3 of instance AND 3 of the AND function block.
Index:
[0] = Input I0
[1] = Input I1
[2] = Input I2
[3] = Input I3
Description:
Display parameter for binary quantity Q = I0 & I1 & I2 & I3 of instance AND 3 of the AND function block.
Description:
Setting parameter for the run-time group in which the instance AND 3 of the AND function block is to be called.
Value:
1:
Run-time group 1
2:
Run-time group 2
3:
Run-time group 3
4:
Run-time group 4
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
Description:
Setting parameter for the run sequence of instance AND 3 within the run-time group set in p20044.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20041
AND 2 run sequence / AND 2 RunSeq
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2710
Min Max
Factory
setting
0 32000
30
p20042[0...3]
BI: AND 3 inputs / AND 3 inputs
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7210
Min Max
Factory
setting
- - 0
r20043
BO: AND 3 output Q / AND 3 output Q
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7210
Min Max
Factory
setting
- - -
p20044
AND 3 run-time group / AND 3 RTG
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7210
Min Max
Factory
setting
1 9999
9999
p20045
AND 3 run sequence / AND 3 RunSeq
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7210
Min Max
Factory
setting
0 32000
40