2 Parameters
2.2 List of parameters
SINAMICS G120D
472
List Manual (LH14), 01/2016, A5E33842313
Description:
The parameter is used for diagnostics.
Note:
For bit 00 = 1:
At least one Safety parameter has been changed that will only take effect after a POWER ON.
For bit 01 = 1:
Safety functions (basic functions or extended functions) have been enabled and are active.
For bit 02 = 1:
A safety-relevant component has been replaced. Data save required (p0977 = 1 or p0971 = 1 or "copy RAM to
ROM").
Description:
Displays the clock cycle time for the Safety Integrated Basic Functions on processor 1.
Note:
Information regarding the relationship between monitoring clock cycle and response times can be found in the
following references:
- SINAMICS G120 Function Manual Safety Integrated
- technical documentation for the particular product
Description:
Displays the checksum for tracking changes for Safety Integrated.
These are additional checksums that are created to track changes (fingerprint for the "safety logbook" functionality) to
safety parameters (that are relevant for checksums).
Index:
[0] = SI checksum to track functional changes
[1] = SI checksum to track hardware-specific changes
Dependency:
Refer to: p9601, p9729, p9799
Refer to: F01690
Description:
Displays the time stamps for the checksums for tracking changes for Safety Integrated.
r9776
SI diagnostics / SI diag
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Safety parameter changed POWER ON
required
Yes
No
-
01
Safety functions enabled
Yes
No
-
02
Safety component replaced and data save
required
Yes
No
-
r9780
SI monitoring clock cycle (processor 1) / SI mon_clk cyc P1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2802
Min Max
Factory
setting
- [ms]
- [ms]
- [ms]
r9781[0...1]
SI checksum to check changes (processor 1) / SI chg chksm P1
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
r9782[0...1]
SI time stamp to check changes (processor 1) / SI chg t P1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [h]
- [h]
- [h]