2 Parameters
2.2 List of parameters
SINAMICS G120D
276
List Manual (LH14), 01/2016, A5E33842313
Notice:
Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types.
A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
Description:
Selects the PZD (actual values) with double word format to be sent to the fieldbus controller.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11] = PZD 12 + 13
[12] = PZD 13 + 14
[13] = PZD 14 + 15
[14] = PZD 15 + 16
[15] = PZD 16 + 17
Dependency:
Refer to: p2051
Notice:
A BICO interconnection for a single PZD can only take place either on p2051 or p2061.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Displays the PZD (actual values) with double word format sent to the fieldbus controller.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11] = PZD 12 + 13
[12] = PZD 13 + 14
[13] = PZD 14 + 15
[14] = PZD 15 + 16
[15] = PZD 16 + 17
p2061[0...15]
CI: PROFIBUS PZD send double word / PZD send DW
Access level:
3
Calculated:
-
Data type:
U32 / Integer32
Can be changed:
U, T
Scaling:
4000H
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2470
Min Max
Factory
setting
- - 0
r2063[0...15]
PROFIdrive diagnostics PZD send double word / Diag send DW
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2450, 2470
Min Max
Factory
setting
- - -