2 Parameters
2.2 List of parameters
SINAMICS G120D
328
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets the signal source for the scaling value of the technology controller.
Dependency:
Refer to: p2295
Description:
Sets the signal source for the maximum limiting of the technology controller.
Dependency:
Refer to: p2291
Note:
In order that the output of the technology controller does not exceed the maximum speed limit, its upper limit p2297
should be connected to the actual maximum speed r1084.
In mode p2251 = 1, p2299 must also be connected to the output of the ramp-function generator r1150.
Description:
Sets the signal source for the minimum limiting of the technology controller.
Dependency:
Refer to: p2292
Note:
If the technology controller is rotated in a negative direction in mode p2251 = 0, its lower limit p2298 should be
connected to the actual minimum speed r1087.
In mode p2251 = 1, p2299 must also be connected to the output of the ramp-function generator r1150.
Description:
Sets the signal source for the offset of the output limiting of the technology controller.
Note:
In mode p2251 = 1, p2299 must be connected to the output of ramp-function generator r1150 so that the technology
controller stops when the speed limits are reached (see also p2297, p2298).
Description:
Sets the start value for the output of the technology controller.
If the drive is switched on and the technology controller is already enabled (see p2200, r0056.3), then its output
signal r2294 first goes to the start value p2302, before the controller starts to operate.
p2296[0...n]
CI: Technology controller output scaling / Tec_ctrl outp scal
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
- - 2295[0]
p2297[0...n]
CI: Technology controller maximum limit signal source / Tec_ctrMaxLimS_src
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
- - 1084[0]
p2298[0...n]
CI: Technology controller minimum limit signal source / Tec_ctrl min_l s_s
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
- - 1087[0]
p2299[0...n]
CI: Technology controller limit offset / Tech_ctrl lim offs
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
U, T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
- - 0
p2302
Technology controller output signal starting value / Tec_ctr start val
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7958
Min Max
Factory
setting
0.00 [%]
200.00 [%]
0.00 [%]