![Siemens SINAMICS G120D CU240D-2 DP Manual Download Page 414](http://html.mh-extra.com/html/siemens/sinamics-g120d-cu240d-2-dp/sinamics-g120d-cu240d-2-dp_manual_381563414.webp)
2 Parameters
2.2 List of parameters
SINAMICS G120D
414
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets the alarm threshold for monitoring the motor temperature for motor temperature models 1 and 3.
The stator winding temperature (r0632) is used to initiate the signal.
The following applies for temperature model 1 (I2t):
- only effective from firmware version 4.7 SP6 and p0612.8 = 1.
- Alarm A07012 is output after the alarm threshold is exceeded.
- when commissioning a catalog motor for the first time, the threshold value is copied from p0605 to p5390.
The following applies for temperature model 3:
- after the alarm threshold is exceeded, alarm A07012 is output and a calculated delay time (t = p5371/p5381) is
started.
- if the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011
is output.
Dependency:
Refer to: r0034, p0605, p0612, r0632, p5391
Refer to: F07011, A07012, A07014
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis is 2 K.
Description:
Sets the fault threshold for monitoring the motor temperature for motor temperature models 1 and 3.
Fault F07011 is output after the fault threshold is exceeded.
The stator winding temperature (r0632) is used to initiate the signal.
The following applies for temperature model 1 (I2t):
- only effective from firmware version 4.7 SP6 and p0612.8 = 1.
- when commissioning a catalog motor for the first time, the threshold value is copied from p0615 to p5391.
Dependency:
Refer to: r0034, p0612, p0615, r0632, p5390
Refer to: F07011, A07014
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The hysteresis is 2 K.
Description:
Displays the ambient temperature for motor temperature model 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p0613.
Dependency:
Refer to: r0034
Note:
Users cannot see and change parameter p0613 (only Siemens internal).
p5390[0...n]
Mot_temp_mod 1/3 alarm threshold / A thresh
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
21_1
Unit selection:
p0505
Func. diagram:
8017
Min Max
Factory
setting
0.0 [°C]
200.0 [°C]
110.0 [°C]
p5391[0...n]
Mot_temp_mod 1/3 fault threshold / F thresh
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
21_1
Unit selection:
p0505
Func. diagram:
8017
Min Max
Factory
setting
0.0 [°C]
200.0 [°C]
120.0 [°C]
r5397
Mot_temp_mod 3 ambient temperature image p0613 / AmbTmp image p0613
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
21_1
Unit selection:
p0505
Func. diagram:
8019
Min Max
Factory
setting
- [°C]
- [°C]
- [°C]