2 Parameters
2.2 List of parameters
SINAMICS G120D
126
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets the response threshold for the wire breakage monitoring of the analog inputs.
The unit for the parameter value depends on the set analog input type.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Dependency:
For the following analog input type, the wire breakage monitoring is active:
p0756[0...1] = 1 (unipolar voltage input monitored (+2 V ... +10 V)), unit [V]
Refer to: p0756
Note:
AI: Analog Input
When p0761 = 0, wire breakage monitoring is not carried out.
Description:
Sets the delay time for the wire breakage monitoring of the analog inputs.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
AI: Analog Input
Description:
Determines the width of the dead zone at the analog input.
Analog input type unipolar (e.g. 0 ... +10 V):
The dead zone starts with the characteristic value x1/y1 (p0757/p0758).
Analog input type bipolar (e.g. -10 V ... +10 V):
The dead zone is located at the symmetrical center between characteristic value x1/y1 (p0757/p0758) and x2/y2
(p0759/p0760). The set value doubles the dead zone.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
AI: Analog Input
T: Terminal
Description:
Sets the simulation mode for digital inputs.
p0761[0...1]
CU analog inputs wire breakage monitoring response threshold / CU WireBrkThresh
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568
Min Max
Factory
setting
0.00 20.00
2.00
p0762[0...1]
CU analog inputs wire breakage monitoring delay time / CU wire brk t_del
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568
Min Max
Factory
setting
0 [ms]
1000 [ms]
100 [ms]
p0764[0...1]
CU analog inputs dead zone / CU AI dead zone
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2251
Min Max
Factory
setting
0.000 20.000
0.000
p0795
CU digital inputs simulation mode / CU DI simulation
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2201, 2210, 2256
Min Max
Factory
setting
-
-
0000 0000 0000 0000 bin