SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
89
2 Parameters
2.2 List of parameters
Description:
Displays the effective filter time for a squarewave encoder.
The filter time is set using p0438.
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency:
Refer to: p0438
Note:
A value of zero is displayed if an encoder is not present.
Description:
Sets the measuring time for evaluating zero speed.
If no pulses are detected from track A/B during this time, a speed actual value of zero is output.
Dependency:
Refer to: r0452
Note:
This function is required for slow-running motors so that actual speeds close to zero can be output correctly.
Description:
Displays the encoder configuration supported by the Sensor Module.
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency:
Refer to: p0404
Note:
ZM: Zero mark
This parameter is only used for diagnostics.
A value of zero is displayed if an encoder is not present.
Description:
Displays the encoder configuration supported by the Sensor Module.
r0452[0...2]
Squarewave encoder filter time display / Enc t_filt displ
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [µs]
- [µs]
- [µs]
p0453[0...n]
Pulse encoder evaluation zero speed measuring time / Enc_ev n_0 t_meas
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.10 [ms]
10000.00 [ms]
1000.00 [ms]
r0456[0...2]
Encoder configuration supported / Enc_config supp
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Linear encoder
Yes
No
-
03
Track A/B sq-wave
Yes
No
-
12
Equidistant zero mark
Yes
No
-
13
Irregular zero mark
Yes
No
-
14
Distance-coded zero mark
Yes
No
-
21
Voltage level 24 V
Yes
No
-
r0456[0...2]
Encoder configuration supported / Enc_config supp
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -