SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
167
2 Parameters
2.2 List of parameters
Description:
Sets the signal source for the supplementary setpoint.
Dependency:
Refer to: p1076, r1077, r1078
Description:
Sets the signal source for scaling the supplementary setpoint.
Description:
Displays the effective supplementary setpoint. The value shown is the additional setpoint after scaling.
Description:
Displays the total effective setpoint.
The value indicates the sum of the effective main setpoint and supplementary setpoint.
Description:
Sets the lowest possible motor speed.
This value is not undershot in operation.
Dependency:
Refer to: p1106
Notice:
The effective minimum speed is formed from p1080 and p1106.
Note:
The parameter value applies for both motor directions.
In exceptional cases, the motor can operate below this value (e.g. when reversing).
p1075[0...n]
CI: Suppl setp / Suppl setp
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3001, 3030
Min Max
Factory
setting
- - 0
p1076[0...n]
CI: Supplementary setpoint scaling / Suppl setp scal
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3001, 3030
Min Max
Factory
setting
- - 1
r1077
CO: Supplementary setpoint effective / Suppl setpoint eff
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3030
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
r1078
CO: Total setpoint effective / Total setpoint eff
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3030
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]
p1080[0...n]
Minimum speed / n_min
Access level:
1
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(1), T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3050, 8022
Min Max
Factory
setting
0.000 [rpm]
19500.000 [rpm]
0.000 [rpm]