2 Parameters
2.2 List of parameters
SINAMICS G120D
150
List Manual (LH14), 01/2016, A5E33842313
Note:
If value = 1:
Reset is immediately executed and communications interrupted.
After communications have been established, check the reset operation (refer below).
If value = 2:
Help to check the reset operation.
Firstly, set p0972 = 2 and then read back. Secondly, set p0972 = 1 (it is possible that this request is possibly no
longer acknowledged). The communication is then interrupted.
After communications have been established, check the reset operation (refer below).
If value = 3:
The reset is executed after interrupting cyclic communication. This setting is used to implement a synchronized reset
by a control for several drive units.
If cyclic communication is not active, then the reset is immediately executed.
After communications have been established, check the reset operation (refer below).
To check the reset operation:
After the drive unit has been restarted and communications have been established, read p0972 and check the
following:
p0972 = 0? --> the reset was successfully executed.
p0972 = 0? --> the reset was not executed.
Description:
Displays the actual position encoder used according to PROFIdrive.
Index:
[0] = Header
[1] = Type encoder 1
[2] = Resolution enc 1
[3] = Shift factor G1_XIST1
[4] = Shift factor G1_XIST2
[5] = Distinguishable revolutions encoder 1
[6...10] = Reserved
[11] = Type encoder 2
[12] = Resolution enc 2
[13] = Shift factor G2_XIST1
[14] = Shift factor G2_XIST2
[15] = Distinguishable revolutions encoder 2
[16...20] = Reserved
[21] = Type encoder 3
[22] = Resolution enc 3
[23] = Shift factor G3_XIST1
[24] = Shift factor G3_XIST2
[25] = Distinguishable revolutions encoder 3
[26...30] = Reserved
Note:
Information about the individual indices can be taken from the following literature:
PROFIdrive Profile Drive Technology
Description:
Displays the parameters that exist for this drive.
Dependency:
Refer to: r0981, r0989
r0979[0...30]
PROFIdrive encoder format / PD encoder format
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
4704
Min Max
Factory
setting
- - -
r0980[0...299]
List of existing parameters 1 / List avail par 1
Access level:
4
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory