SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
433
2 Parameters
2.2 List of parameters
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
ODVA: Open DeviceNet Vendor Association
Description:
Sets the STOP mode for the Ethernet/IP ODVA profile (p8980 = 1).
Value:
0:
OFF1
1:
OFF2
Dependency:
Refer to: p8980
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description:
Sets the scaling for the speed for Ethernet/IP ODVA profile (p8980 = 1).
Value:
123:
32
124:
16
125:
8
126:
4
127:
2
128:
1
129:
0.5
130:
0.25
131:
0.125
132:
0.0625
133:
0.03125
Dependency:
Refer to: p8980
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description:
Sets the scaling for the torque for Ethernet/IP ODVA profile (p8980 = 1).
Value:
123:
32
124:
16
125:
8
126:
4
127:
2
128:
1
129:
0.5
130:
0.25
131:
0.125
132:
0.0625
133:
0.03125
p8981
Ethernet/IP ODVA STOP mode / Eth/IP ODVA STOP
CU240D-2_PN
CU240D-2_PN_F
CU250D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2473
Min Max
Factory
setting
0 1 0
p8982
Ethernet/IP ODVA speed scaling / Eth/IP ODVA n scal
CU240D-2_PN
CU240D-2_PN_F
CU250D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
123 133 128
p8983
Ethernet/IP ODVA torque scaling / Eth/IP ODVA M scal
CU240D-2_PN
CU240D-2_PN_F
CU250D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
123 133 128