4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G120D
822
List Manual (LH14), 01/2016, A5E33842313
A01066
Buffer memory: 70% fill level reached or exceeded
Message class:
General drive fault (19)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The non-volatile buffer memory for parameter changes is filled to at least 70%.
This can also occur if the buffer memory is active (p0014 = 1) and parameters are continually changed via a fieldbus
system.
Remedy:
If required, de-activate and clear the buffer memory (p0014 = 0).
If required, clear the buffer memory (p0014 = 2).
In the following cases, the entries in the buffer memory are transferred into the ROM and then the buffer memory is
cleared:
- p0971 = 1
- switch off/switch on the Control Unit
See also: p0014 (Buffer memory mode)
A01067
Buffer memory: 100 % fill level reached
Message class:
General drive fault (19)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The non-volatile buffer memory for parameter changes is filled to 100%.
All additional parameter changes will no longer be taken into account in the non-volatile buffer memory. However,
parameter changes can still be made in the volatile memory (RAM).
This can also occur if the buffer memory is active (p0014 = 1) and parameters are continually changed via a fieldbus
system.
Remedy:
If required, de-activate and clear the buffer memory (p0014 = 0).
If required, clear the buffer memory (p0014 = 2).
In the following cases, the entries in the buffer memory are transferred into the ROM and then the buffer memory is
cleared:
- p0971 = 1
- switch off/switch on the Control Unit
See also: p0014 (Buffer memory mode)
F01068
CU: Data memory memory overflow
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The utilization for a data memory area is too large.
Fault value (r0949, interpret binary):
Bit 0 = 1: High-speed data memory 1 overloaded
Bit 1 = 1: High-speed data memory 2 overloaded
Bit 2 = 1: High-speed data memory 3 overloaded
Bit 3 = 1: High-speed data memory 4 overloaded
Remedy:
- de-activate the function module.
- de-activate drive object.
- remove the drive object from the target topology.
A01069
Parameter backup and device incompatible
Message class:
Error in the parameterization / configuration / commissioning procedure (18)
Reaction:
NONE
Acknowledge:
NONE
Cause:
The parameter backup on the memory card and the drive unit do not match.
The module boots with the factory settings.
Example:
Devices A and B. are not compatible and a memory card with the parameter backup for device A is inserted in device