2 Parameters
2.2 List of parameters
SINAMICS G120D
400
List Manual (LH14), 01/2016, A5E33842313
Note:
For bit 00:
All of the help functions for long stator motors can be enabled/disabled using this bit.
For bit 01:
When the bit is set, bit 14 (parking encoder active) is set to 0 in the encoder status word GX_ZSW independent of
whether the encoder is parked or not.
Description:
Exits quick commissioning (p0010 = 1) with automatic calculation of all parameters of all existing drive data sets that
depend on the entries made during quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning.
The interconnections of PROFIBUS PZD telegram selection (p0922) and the interconnections via p15 and p1500 are
re-established and all of the dependent motor, open-loop and control-loop control parameters are calculated
(corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p15 and p1500 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the calculations associated with the motor, open-loop and closed-loop control parameters
corresponding to p0340 = 1.
Value:
0:
No quick parameterization
1:
Quick parameterization after parameter reset
2:
Quick parameterization (only) for BICO and motor parameters
3:
Quick parameterization for motor parameters (only)
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
When the calculations have been completed, p3900 and p0010 are automatically reset to a value of zero.
When calculating motor, open-loop and closed-loop control parameters (such as for p0340 = 1) parameters
associated with a selected Siemens catalog motor are not overwritten.
If a catalog motor has not been selected (p0300), then the following parameters are reset with p3900 > 0 in order to
restore the situation that applied when commissioning the drive for the first time:
induction motor: p0320, p0352, p0362 ... p0369, p0604, p0605, p0626 ... p0628
synchronous motor: p0326, p0327, p0352, p0604, p0605
Description:
Displays the commissioning steps that have been carried out.
p3900
Completion of quick commissioning / Compl quick_comm
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C(1)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 3 0
r3925[0...n]
Identification final display / Ident final_disp
Access level:
3
Calculated:
p0340 = 1
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Motor/control parameters calculated (p0340
= 1, p3900 > 0)
Yes
No
-
02
Motor data identification carried out at
standstill (p1910 = 1)
Yes
No
-
03
Rotating measurement carried out (p1960 =
1, 2)
Yes
No
-
08
Motor identification data have been
automatically backed up
Yes
No
-
11
Automatic parameterization as standard
drive control
Yes
No
-