2 Parameters
2.2 List of parameters
SINAMICS G120D
272
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value:
0:
SINAMICS
1:
VIK-NAMUR
Notice:
For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
Every change only becomes effective after a POWER ON.
Description:
Displays the PROFIdrive PZD state.
Dependency:
Refer to: p2044
Note:
When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
Dependency:
Refer to: r2043
Refer to: F01910
Description:
Sets the additional monitoring time to monitor the process data received via PROFIBUS.
Enables short bus faults to be compensated.
If no process data is received within this time, then an appropriate message is output.
Dependency:
Refer to: F01910
Note:
For controller STOP, the additional monitoring time is not effective.
p2042
PROFIBUS Ident Number / PB Ident No.
CU240D-2_DP
CU240D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 1 0
r2043.0...2
BO: PROFIdrive PZD state / PD PZD state
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2410
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Setpoint failure
Yes
No
-
02
Fieldbus oper
Yes
No
-
p2044
PROFIdrive fault delay / PD fault delay
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2410
Min Max
Factory
setting
0 [s]
100 [s]
0 [s]
p2047
PROFIBUS additional monitoring time / PB suppl t_monit
CU240D-2_DP
CU240D-2_DP_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2410
Min Max
Factory
setting
0 [ms]
20000 [ms]
0 [ms]