2 Parameters
2.2 List of parameters
SINAMICS G120D
200
List Manual (LH14), 01/2016, A5E33842313
Description:
Limiting the voltage setpoint.
This means that the output voltage can be reduced with respect to the calculated maximum voltage r0071 and the
start of field weakening.
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Note:
The output voltage is only limited if, as a result of p1331, the maximum output voltage (r0071) is fallen below.
Description:
Sets the starting frequency at which FCC (Flux Current Control) is activated.
Dependency:
The correct operating mode must be set (p1300 = 1, 6).
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Warning:
An excessively low value can result in instability.
Note:
For p1333 = 0 Hz, the FCC starting frequency is automatically set to 6 % of the rated motor frequency.
Description:
Sets the starting frequency of the slip compensation.
Dependency:
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Note:
For p1334 = 0, the starting frequency of the slip compensation is automatically set to 6 % of the rated motor
frequency.
Description:
Sets the setpoint for slip compensation in [%] referred to r0330 (motor rated slip).
p1335 = 0.0 %: Slip compensation de-activated.
p1335 = 100.0 %: The slip is completely compensated.
Dependency:
Prerequisite for a precise slip compensation for p1335 = 100 % are the precise motor parameters (p0350 ... p0360).
If the parameters are not precisely known, a precise compensation can be achieved by varying p1335.
For U/f control types with Eco optimization (4 and 7), the slip compensation must be activated in order to guarantee
correct operation.
Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
p1331[0...n]
Voltage limiting / U_lim
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
5_1
Unit selection:
p0505
Func. diagram:
6300
Min Max
Factory
setting
50.00 [Vrms]
2000.00 [Vrms]
1000.00 [Vrms]
p1333[0...n]
U/f control FCC starting frequency / U/f FCC f_start
Access level:
3
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6301
Min Max
Factory
setting
0.00 [Hz]
3000.00 [Hz]
0.00 [Hz]
p1334[0...n]
U/f control slip compensation starting frequency / Slip comp start
Access level:
3
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6310
Min Max
Factory
setting
0.00 [Hz]
3000.00 [Hz]
0.00 [Hz]
p1335[0...n]
Slip compensation scaling / Slip comp scal
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
6300, 6310
Min Max
Factory
setting
0.0 [%]
600.0 [%]
0.0 [%]