2 Parameters
2.2 List of parameters
Dependency:
Refer to: p0043
Note:
The signal can be displayed as process variable (scaling: 1 = 1 Wh).
This is enabled in p0043.
The display is also reset with p0040 = 1.
If an enable is present in r0043 when the Control Unit powers up, then the value from r0039 is transferred into r0042.
As r0039 serves as a reference signal for r0042, due to format reasons, the process energy display can only process
values of r0039 up to 2147483 kWh. r0039 should also be reset using this value.
Description:
Sets the signal source to enable/reset the process energy display in r0042.
BI: p0043 = 1 signal:
The process energy display is enabled in r0042.
Dependency:
Refer to: r0042
Description:
Sets the smoothing time constant for the following display values:
r0063[1], r0068[1], r0080[1], r0082[1].
Description:
Display and BICO output for missing enable signals that are preventing the closed-loop drive control from being
commissioned.
p0043
BI: Enable energy usage display / Enab energy usage
Access level:
2
Calculated:
-
Data type:
U32 / Binary
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - 0
p0045
Display values smoothing time constant / Disp_val T_smooth
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
6714, 8012
Min Max
Factory
setting
0.00 [ms]
10000.00 [ms]
4.00 [ms]
r0046.0...31
CO/BO: Missing enable sig / Missing enable sig
Access level:
1
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2634
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
OFF1 enable missing
Yes
No
7954
01
OFF2 enable missing
Yes
No
-
02
OFF3 enable missing
Yes
No
-
03
Operation enable missing
Yes
No
-
04
DC braking enable missing
Yes
No
-
08
Safety enable missing
Yes
No
-
10
Ramp-function generator enable missing
Yes
No
-
11
Ramp-function generator start missing
Yes
No
-
12
Setpoint enable missing
Yes
No
-
16
OFF1 enable internal missing
Yes
No
-
17
OFF2 enable internal missing
Yes
No
-
18
OFF3 enable internal missing
Yes
No
-
19
Pulse enable internal missing
Yes
No
-
20
DC braking internal enable missing
Yes
No
-
21
Power unit enable missing
Yes
No
-
26
Drive inactive or not operational
Yes
No
-
27
De-magnetizing not completed
Yes
No
-
28
Brake open missing
Yes
No
-
30
Speed controller inhibited
Yes
No
-
31
Jog setpoint active
Yes
No
-