2 Parameters
2.2 List of parameters
SINAMICS G120D
270
List Manual (LH14), 01/2016, A5E33842313
Index:
[0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
Description:
Sets the communication protocol for the field bus interface.
Value:
0:
No protocol
3:
PROFIBUS
Notice:
For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description:
Sets the communication protocol for the field bus interface.
Value:
0:
No protocol
7:
PROFINET
10:
EtherNet/IP
Notice:
For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description:
Displays the effective control word 1 (STW1) of the drive for the master control.
p2030
Field bus int protocol selection / Field bus protocol
CU240D-2_DP
CU240D-2_DP_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9310
Min Max
Factory
setting
0 3 3
p2030
Field bus int protocol selection / Field bus protocol
CU240D-2_PN
CU240D-2_PN_F
CU250D-2_PN_F
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9310
Min Max
Factory
setting
0 10
7
r2032
Master control control word effective / PcCtrl STW eff
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
ON/OFF1
Yes
No
-
01
OC / OFF2
Yes
No
-
02
OC / OFF3
Yes
No
-
03
Operation enable
Yes
No
-
04
Ramp-function generator enable
Yes
No
-
05
Start ramp-function generator
Yes
No
-
06
Speed setpoint enable
Yes
No
-
07
Acknowledge fault
Yes
No
-
08
Jog bit 0
Yes
No
3030