SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
393
2 Parameters
2.2 List of parameters
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 5 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3329
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 5 as a [%].
Dependency:
Refer to: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3328
Note:
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
Description:
The friction characteristic is defined by 10 value pairs.
This parameter specifies the n coordinate of the 1st value pair of the friction characteristic.
Dependency:
Refer to: p3830, p3845
Description:
The friction characteristic is defined by 10 value pairs.
This parameter specifies the n coordinate of the 2nd value pair of the friction characteristic.
Dependency:
Refer to: p3831, p3845
p3328[0...n]
Fluid flow machine power point 5 / Fluid_mach P5
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 100.00
100.00
p3329[0...n]
Fluid flow machine speed point 5 / Fluid_mach n5
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0.00 100.00
100.00
p3820[0...n]
Friction characteristic value n0 / Friction n0
Access level:
2
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
7010
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
15.00 [rpm]
p3821[0...n]
Friction characteristic value n1 / Friction n1
Access level:
2
Calculated:
p0340 = 1,3,5
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
7010
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
30.00 [rpm]