2 Parameters
2.2 List of parameters
SINAMICS G120D
68
List Manual (LH14), 01/2016, A5E33842313
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
The following parameters are influenced using p0340:
p0340 = 1:
--> All of the parameters influenced for p0340 = 2, 3, 4, 5
--> p0341, p0342, p0344, p0612, p0640, p1082, p1231, p1232, p1333, p1349, p1611, p1654, p1726, p1825, p1828
... p1832, p1909, p1959, p2000, p2001, p2002, p2003, p3927, p3928
p0340 = 2:
--> p0350, p0354 ... p0360
--> p0625 (matching p0350), p0626 ... p0628
p0340 = 3:
--> All of the parameters influenced for p0340 = 4, 5
--> p0346, p0347, p0622, p1320 ... p1327, p1582, p1584, p1616, p1755, p1756, p2178
p0340 = 4:
--> p1290, p1292, p1293, p1338, p1339, p1340, p1341, p1345, p1346, p1461, p1463, p1464, p1465, p1470, p1472,
p1703, p1715, p1717, p1740, p1756, p1764, p1767, p1780, p1781, p1783, p1785, p1786, p1795
p0340 = 5:
--> p1037, p1038, p1520, p1521, p1530, p1531, p1574, p1750, p1759, p1802, p1803, p2140, p2142, p2148, p2150,
p2157, p2159, p2161, p2162, p2163, p2164, p2170, p2175, p2177, p2179, p2194
Note:
p0340 = 1 contains the calculations of p0340 = 2, 3, 4, 5.
p0340 = 2 calculates the motor parameters (p0350 ... p0360).
p0340 = 3 contains the calculations of p0340 = 4, 5.
p0340 = 4 only calculates the controller parameters.
p0340 = 5 only calculates the controller limits.
When quick commissioning is exited using p3900 > 0, p0340 is automatically set to 1.
At the end of the calculations, p0340 is automatically set to 0.
Description:
Sets the motor moment of inertia (without load).
Dependency:
IEC drives (p0100 = 0): unit kg m^2
NEMA drives (p0100 = 1): unit lb ft^2
The parameter value is included, together with p0342, in the rated starting time of the motor.
Refer to: p0342, r0345
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
The product of p0341 * p0342 is used when the speed controller (p0340 = 4) is calculated automatically.
Description:
Sets the ratio between the total moment of inertia/mass (load + motor) and the intrinsic motor moment of inertia/mass
(no load).
Dependency:
This means that together with p0341, the rated starting (accelerating time) of the motor is calculated for a vector
drive.
Refer to: p0341, r0345, p1498
Note:
The product of p0341 * p0342 is used when the speed controller (p0340 = 4) is calculated automatically.
p0341[0...n]
Motor moment of inertia / Mot M_mom of inert
Access level:
3
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
25_1
Unit selection:
p0100
Func. diagram:
6020, 6030, 6031
Min Max
Factory
setting
0.000000 [kgm²]
100000.000000 [kgm²]
0.000000 [kgm²]
p0342[0...n]
Ratio between the total and motor moment of inertia / Mot MomInert Ratio
Access level:
3
Calculated:
p0340 = 1
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
6020, 6030, 6031
Min Max
Factory
setting
1.000 10000.000
1.000