2 Parameters
2.2 List of parameters
Description:
Displays the operating hours for the corresponding motor.
The motor operating time counter continues to run when the pulses are enabled. When the pulse enable is
withdrawn, the counter is held and the value saved.
Dependency:
Refer to: p0651
Refer to: A01590
Note:
For p0651 = 0, the operating hours counter is disabled.
The operating hours counter in p0650 can only be reset to 0.
The operating hours counter only runs with drive data set 0 and 1 (DDS).
Description:
Sets the service/maintenance intervals in hours for the appropriate motor.
An appropriate fault is output when the operating hours set here are reached.
Dependency:
Refer to: p0650
Refer to: A01590
Note:
For p0651 = 0, the operating hours counter is disabled.
When setting p0651 to 0, then p0650 is automatically set to 0.
The operating hours counter only runs with drive data set 0 and 1 (DDS).
If there is no temperature monitor, then interconnect to a fixed value.
For index 3:
When the binector input is interconnected, precharging is switched-on independent of the magnitude of the
precharging threshold.
Description:
Displays the number of inputs and outputs.
Index:
[0] = Number of digital inputs
[1] = Number of digital outputs
[2] = Number of digital input/outputs bidirectional
[3] = Number of analog inputs
[4] = Number of analog outputs
Description:
Displays the actual value at the digital inputs.
p0650[0...n]
Actual motor operating hours / Mot t_oper act
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
T
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 [h]
4294967295 [h]
0 [h]
p0651[0...n]
Motor operating hours maintenance interval / Mot t_op maint
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
T
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 [h]
150000 [h]
0 [h]
r0720[0...4]
CU number of inputs and outputs / CU I/O count
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2119
Min Max
Factory
setting
- - -
r0721
CU digital inputs terminal actual value / CU DI term act val
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
2
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2201, 2210, 2256
Min Max
Factory
setting
- - -