![Siemens SINAMICS G120D CU240D-2 DP Manual Download Page 170](http://html.mh-extra.com/html/siemens/sinamics-g120d-cu240d-2-dp/sinamics-g120d-cu240d-2-dp_manual_381563170.webp)
2 Parameters
2.2 List of parameters
SINAMICS G120D
170
List Manual (LH14), 01/2016, A5E33842313
Description:
Sets skip speed 1.
Dependency:
Refer to: p1092, p1093, p1094, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Note:
The skip (suppression) speeds can be used to prevent the effects of mechanical resonance.
Description:
Sets skip speed 2.
Dependency:
Refer to: p1091, p1093, p1094, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Description:
Sets skip speed 3.
Dependency:
Refer to: p1091, p1092, p1094, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Description:
Sets skip speed 4.
Dependency:
Refer to: p1091, p1092, p1093, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Description:
Sets the signal source for scaling the skip speeds.
Dependency:
Refer to: p1091, p1092, p1093, p1094
p1091[0...n]
Skip speed 1 / n_skip 1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3050
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1092[0...n]
Skip speed 2 / n_skip 2
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3050
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1093[0...n]
Skip speed 3 / n_skip 3
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3050
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1094[0...n]
Skip speed 4 / n_skip 4
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
p2000
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3050
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1098[0...n]
CI: Skip speed scaling / n_skip scal
Access level:
3
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
PERCENT
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3050
Min Max
Factory
setting
- - 1