2 Parameters
2.2 List of parameters
SINAMICS G120D
86
List Manual (LH14), 01/2016, A5E33842313
Example:
p0435 = 1014
--> The evaluation is switched in and the alarm bit is at position 14 with a low level.
p0435 = 1114
--> The evaluation is switched in and the alarm bit is at position 14 with a high level.
Description:
Sets the position and parity of the parity bit in the SSI protocol.
Notice:
The bit may only be positioned before (p0446) or after (p0448) the absolute value in the SSI protocol.
Note:
Value = dcba
ba: Position of the parity bit in the protocol (0 ... 63).
c: Parity (0: even, 1: uneven).
d: State of the evaluation (0: Off, 1: On).
Example:
p0436 = 1015
--> The evaluation is switched in and the parity bit is at position 15 with even parity.
p0436 = 1115
--> The evaluation is switched in and the parity bit is at position 15 with uneven parity.
Description:
Sets the extended configuration of the Sensor Module.
Dependency:
Refer to: p0430, r0459
Note:
A value of zero is displayed if an encoder is not present.
For bit 00:
When the data logger (trace) is activated, in the case of a fault, data before and after the event are recorded (traced)
and saved in files on the non-volatile memory medium. Experts can then evaluate this data.
For bit 01:
If bit = 0, the zero mark is evaluated by ANDing tracks A and B and the zero mark.
For bit = 1, the zero mark is evaluated depending on the direction of rotation detected. For a positive direction of
rotation, the positive edge of the zero mark is considered and for a negative direction of rotation, the negative edge of
the zero mark.
p0436[0...n]
Encoder SSI parity bit / Enc SSI parity bit
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 65535
0
p0437[0...n]
Sensor Module configuration extended / SM config ext
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
C(4)
Scaling:
-
Dyn. index:
EDS, p0140
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
-
-
0000 0000 0000 0000 0000 1000 0000
0000 bin
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Data logger
Yes
No
-
01
Zero mark edge detection
Yes
No
-
02
Correction position actual value XIST1
Yes
No
-
04
Edge evaluation bit 0
Yes
No
-
05
Edge evaluation bit 1
Yes
No
-
06
Freeze the speed actual value for dn/dt
errors
Yes
No
-
11
Fault handling after PROFIdrive
Yes
No
-
12
Activate additional messages
Yes
No
-
13
Support absolute position for incremental
encoder
Yes
No
4750
26
Deselect track monitoring
Yes
No
-