2 Parameters
2.2 List of parameters
SINAMICS G120D
74
List Manual (LH14), 01/2016, A5E33842313
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the x coordinate (magnetizing current) for the 3rd value pair of the characteristic.
Sets the third magnetization current of the saturation characteristic in [%] with reference to the rated magnetization
current (r0331).
Dependency:
The following applies for the magnetizing currents:
p0366 < p0367 < p0368 < p0369
Refer to: p0364
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description:
The saturation characteristics (flux as a function of the magnetizing current) is defined using 4 points.
This parameter specifies the x coordinate (magnetizing current) for the 4th value pair of the characteristic.
Sets the fourth magnetization current of the saturation characteristic in [%] with reference to the rated magnetization
current (r0331).
Dependency:
The following applies for the magnetizing currents:
p0366 < p0367 < p0368 < p0369
Refer to: p0365
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description:
Displays the motor stator resistance at an ambient temperature (p0625).
The value does not include the cable resistance.
Dependency:
Refer to: p0625
Description:
Displays the total cable resistance between power unit and motor, as well as the internal converter resistance.
Dependency:
Refer to: r0238, p0352
p0368[0...n]
Motor saturation characteristic I_mag 3 / Mot sat. I_mag 3
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
6723
Min Max
Factory
setting
5.0 [%]
800.0 [%]
150.0 [%]
p0369[0...n]
Motor saturation characteristic I_mag 4 / Mot sat. I_mag 4
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(3), U, T
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
6723
Min Max
Factory
setting
5.0 [%]
800.0 [%]
210.0 [%]
r0370[0...n]
Motor stator resistance cold / Mot R_stator cold
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [ohm]
- [ohm]
- [ohm]
r0372[0...n]
Cable resistance / Mot R_cable
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
-
Dyn. index:
MDS
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- [ohm]
- [ohm]
- [ohm]