SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
207
2 Parameters
2.2 List of parameters
Description:
Display and BICO output for the status word of the speed controller.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Note:
For bit 16 = 1:
Encoderless open-loop controlled operation not active.
For bit 16 = 0:
Encoderless open-loop controlled operation active.
Description:
Display and BICO output for the status word of the current controller.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
r1407.0...27
CO/BO: Status word speed controller / ZSW n_ctrl
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2522
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
U/f control active
Yes
No
-
01
Encoderless operation active
Yes
No
-
02
Torque control active
Yes
No
6030,
6060,
8011
03
Speed control active
Yes
No
6040
05
Speed controller I component frozen
Yes
No
6040
06
Speed controller I component set
Yes
No
6040
07
Torque limit reached
Yes
No
6060
08
Upper torque limit active
Yes
No
6060
09
Lower torque limit active
Yes
No
6060
10
Droop enabled
Yes
No
6030
11
Speed setpoint limited
Yes
No
6030
12
Ramp-function generator set
Yes
No
-
13
Encoderless operation due to a fault
Yes
No
-
14
I/f control active
Yes
No
-
15
Torque limit reached (without pre-control)
Yes
No
6060
16
Encoderless open-loop controlled operation
not active
Yes
No
-
17
Speed limiting control active
Yes
No
6640
23
Acceleration model activated
Yes
No
-
24
Moment of inertia estimator active
Yes
No
-
25
Load estimate active
Yes
No
-
26
Moment of inertia estimator stabilized
Yes
No
-
27
Accelerated moment of inertia estimator
active
Yes
No
-
r1408.0...14
CO/BO: Status word current controller / ZSW I_ctrl
Access level:
4
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2530
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Current controller act
Active
Not active
-
01
Id control I component limiting
Active
Not active
6714
03
Voltage limiting
Active
Not active
6714
10
Speed adaptation limiting
Active
Not active
-
11
Speed adaptation speed deviation
Out tolerance
In tolerance
6719
12
Motor stalled
Yes
No
-
13
Separately excited synchronous motor is
excited
Yes
No
-
14
Current model SESM magnetizing excit.
current limited to zero
Yes
No
-