SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
521
2 Parameters
2.2 List of parameters
Description:
Setting parameter for the run sequence of instance PDE 0 within the run-time group set in p20161.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description:
Sets the signal source for the input pulse I of instance PDE 1 of the closing delay device.
Description:
Setting parameter for pulse delay time T in milliseconds of instance PDE 1 of the closing delay device.
Description:
Display parameter for output pulse Q of instance PDE 1 of the closing delay device.
Description:
Setting parameter for the run-time group in which instance PDE 1 of the closing delay device is to be called.
Value:
5:
Run-time group 5
6:
Run-time group 6
9999: Do not calculate
Description:
Setting parameter for the run sequence of instance PDE 1 within the run-time group set in p20166.
p20162
PDE 0 run sequence / PDE 0 RunSeq
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7232
Min Max
Factory
setting
0 32000
430
p20163
BI: PDE 1 input pulse I / PDE 1 inp_pulse I
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7232
Min Max
Factory
setting
- - 0
p20164
PDE 1 pulse delay time in ms / PDE 1 t_del ms
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7232
Min Max
Factory
setting
0.00 5400000.00
0.00
r20165
BO: PDE 1 output Q / PDE 1 output Q
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7232
Min Max
Factory
setting
- - -
p20166
PDE 1 run-time group / PDE 1 RTG
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7232
Min Max
Factory
setting
5 9999
9999
p20167
PDE 1 run sequence / PDE 1 RunSeq
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
7232
Min Max
Factory
setting
0 32000
440