SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
307
2 Parameters
2.2 List of parameters
Description:
Sets the delay time for the message "output load not available" (r2197.11 = 1).
Dependency:
Refer to: p2179
Description:
Sets the response when evaluating the load monitoring.
Value:
0:
Load monitoring disabled
1:
A07920 for torque/speed too low
2:
A07921 for torque/speed too high
3:
A07922 for torque/speed out of tolerance
4:
F07923 for torque/speed too low
5:
F07924 for torque/speed too high
6:
F07925 for torque/speed out of tolerance
Dependency:
Refer to: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, p2193, r2198, p3230, p3231
Refer to: A07920, A07921, A07922, F07923, F07924, F07925
Note:
The response to the faults F07923 ... F07925 can be set.
This parameter setting has no effect on the generation of fault F07936.
Description:
Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
Dependency:
The following applies: p2182 < p2183 < p2184
Refer to: p2183, p2184, p2185, p2186
Refer to: A07926
Note:
In order that the load monitoring can reliably respond, the speed threshold p2182 should always be set lower than the
minimum motor speed to be monitored.
Description:
Sets the speed/torque envelope curve for load monitoring.
p2180[0...n]
Output load detection delay time / Out_load det t_del
Access level:
3
Calculated:
-
Data type:
Unsigned16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8022
Min Max
Factory
setting
0 [ms]
10000 [ms]
2000 [ms]
p2181[0...n]
Load monitoring response / Load monit resp
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
8013
Min Max
Factory
setting
0 6 0
p2182[0...n]
Load monitoring speed threshold value 1 / n_thresh 1
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8013
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
150.00 [rpm]
p2183[0...n]
Load monitoring speed threshold value 2 / n_thresh 2
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
8013
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
900.00 [rpm]