2 Parameters
2.2 List of parameters
SINAMICS G120D
440
List Manual (LH14), 01/2016, A5E33842313
These settings apply to the individual limit values for SLS.
Value:
0:
STOP A
1:
STOP B
Index:
[0] = Limit value SLS1
[1] = Limit value SLS2
[2] = Limit value SLS3
[3] = Limit value SLS4
Dependency:
Refer to: p9331, p9563
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SLS: Safely Limited Speed
Description:
Sets the tolerance for the function "Safe motion direction" (SDI).
This motion in the monitored direction is still permissible before safety message C30716 is initiated.
Dependency:
Refer to: p9365, p9366
Refer to: C30716
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SDI: Safe Direction (safe motion direction)
Description:
Sets the delay time for the function "Safe motion direction" (SDI).
After selecting the SDI function, then for a maximum of this time, motion in the monitored direction is permissible.
This time can therefore be used for braking any motion.
Dependency:
Refer to: p9364, p9366
Refer to: C30716
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The set time is rounded internally to an integer multiple of the monitoring clock cycle.
SDI: Safe Direction (safe motion direction)
Description:
Sets the stop response for the function "Safe motion direction" (SDI).
This setting applies to both directions of motion.
In the case of encoderless motion monitoring (p9306 = 1), only a value of 0 or 1 is permitted.
Value:
0:
STOP A
1:
STOP B
Dependency:
Refer to: p9364, p9365
Refer to: C30716
Note:
SDI: Safe Direction (safe motion direction)
p9364
SI Motion SDI tolerance (processor 2) / SI Mtn SDI tol P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2824
Min Max
Factory
setting
0.001 [°]
360.000 [°]
12.000 [°]
p9365
SI Motion SDI delay time (processor 2) / SI Mtn SDI t P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2824
Min Max
Factory
setting
0.00 [µs]
600000000.00 [µs]
100000.00 [µs]
p9366
SI Motion SDI stop response (processor 2) / SI Mtn SDI Stop P2
CU240D-2_DP_F
CU240D-2_PN_F
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C(95)
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
2824
Min Max
Factory
setting
0 1 1