2 Parameters
2.2 List of parameters
SINAMICS G120D
172
List Manual (LH14), 01/2016, A5E33842313
Dependency:
The selection of the total speed setpoint is automatically interconnected to the status word of the technology
controller (r2349.4) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
Refer to: p1109
Caution:
If the technology controller is to supply the total setpoint using p1109, then it is not permissible to withdraw the
interconnection to its status word (r2349.4).
Description:
Sets the signal source for the total setpoint.
For p1108 = 1 signal, the total setpoint is read in via p1109.
Dependency:
The signal source of the total setpoint is automatically interconnected to the output of the technology controller
(r2294) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
Refer to: p1108
Caution:
If the technology controller is to supply the total setpoint using p1109, then it is not permissible to disable the
interconnection to its output (r2294).
Description:
Sets the signal source to disable the negative direction.
Dependency:
Refer to: p1111
Description:
Sets the signal source to disable the positive direction.
Dependency:
Refer to: p1110
Description:
Displays the speed setpoint after the minimum limiting.
Dependency:
Refer to: p1091, p1092, p1093, p1094, p1101
p1109[0...n]
CI: Total setpoint / Total setp
Access level:
4
Calculated:
-
Data type:
U32 / FloatingPoint32
Can be changed:
T
Scaling:
p2000
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
3030
Min Max
Factory
setting
- - 0
p1110[0...n]
BI: Inhibit negative direction / Inhib neg dir
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2505, 3040
Min Max
Factory
setting
- - 0
p1111[0...n]
BI: Inhibit positive direction / Inhib pos dir
Access level:
3
Calculated:
-
Data type:
U32 / Binary
Can be changed:
T
Scaling:
-
Dyn. index:
CDS, p0170
Unit group:
-
Unit selection:
-
Func. diagram:
2505, 3040
Min Max
Factory
setting
- - 0
r1112
CO: Speed setpoint after minimum limiting / n_set aft min_lim
Access level:
4
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
-
Scaling:
p2000
Dyn. index:
-
Unit group:
3_1
Unit selection:
p0505
Func. diagram:
3050
Min Max
Factory
setting
- [rpm]
- [rpm]
- [rpm]