Description:
Sets the factor for the search speed for flying restart.
The value influences the rate at which the output frequency is changed during a flying restart . A higher value results
in a longer search time.
Recommendation:
For encoderless vector control and motor cables longer than 200 m, set the factor p1203 >= 300 %.
Caution:
An unfavorable parameter value can result in the motor behaving in an uncontrollable fashion.
For vector control, a value that is too low or too high can cause flying restart to become unstable.
Note:
The parameter factory setting is selected so that standard induction motors that are rotating can be found and
restarted as quickly as possible (fast flying restart).
With this pre-setting, if the motor is not found (e.g. for motors that are accelerated as a result of active loads or with
U/f control and low speeds), we recommend that the search rate is reduced (by increasing p1203).
For the flying restart of a reluctance motor, the minimum search velocity is limited (p1203 >= 50 %).
Description:
Displays the status for checking and monitoring flying restart states in the U/f control mode.
Description:
Display and connector output for the status for checking and monitoring flying restart states in the vector control
mode.
p1203[0...n]
Flying restart search rate factor / FlyRst v_Srch Fact
Access level:
3
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
DDS, p0180
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
10 [%]
4000 [%]
100 [%]
r1204.0...13
CO/BO: Flying restart U/f control status / FlyRest Uf st
Access level:
4
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Current impressed
Yes
No
-
01
No current flow
Yes
No
-
02
Voltage input
Yes
No
-
03
Voltage reduced
Yes
No
-
04
Start ramp-function generator
Yes
No
-
05
Wait for execution
Yes
No
-
06
Slope filter act
Yes
No
-
07
Positive gradient
Yes
No
-
08
Current < thresh
Yes
No
-
09
Current minimum
Yes
No
-
10
Search in the positive direction
Yes
No
-
11
Stop after positive direction
Yes
No
-
12
Stop after negative direction
Yes
No
-
13
No result
Yes
No
-
r1205.0...15
CO/BO: Flying restart vector control status / FlyRest vector st
Access level:
4
Calculated:
-
Data type:
Unsigned32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Speed adaptation circuit record angle
Yes
No
-
01
Speed adaptation circuit set gain to 0
Yes
No
-
02
Isd channel enable
Yes
No
-
03
Speed control switched out
Yes
No
-
04
Quadrature arm switched in
Yes
No
-
05
Special transformation active
Yes
No
-