SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
379
2 Parameters
2.2 List of parameters
Dependency:
Refer to: p2571, p2646
Note:
The effective override can differ from the specified override due to limits (e.g. p2571, maximum velocity).
Description:
Displays the current residual distance.
The remaining distance is the distance to still to be moved through up to the end of the actual positioning task.
Dependency:
Refer to: r2665, r2671, r2678
Description:
Displays status word 1 for the basic positioner (EPOS).
Dependency:
Refer to: r2684
Note:
For bit 02, 04, 05, 06, 07:
This signals designate the state after jerk limiting.
For bit 08, 09:
These signals are generated in the "closed-loop position control" function module.
Description:
Displays status word 2 for the basic positioner (EPOS).
r2682
CO: EPOS residual distance to go / Residual distance
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
Integer32
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3635
Min Max
Factory
setting
- [LU]
- [LU]
- [LU]
r2683.0...14
CO/BO: EPOS status word 1 / POS_ZSW1
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3645
Min Max
Factory
setting
- - -
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Tracking mode active
Yes
No
3635,
4020
01
Velocity limiting active
Yes
No
3630
02
Setpoint fixed
Yes
No
3635
03
Set position reached
Yes
No
3635
04
Axis moves forward
Yes
No
3635
05
Axis moves backward
Yes
No
3635
06
Software limit switch minus reached
Yes
No
3635
07
Software limit switch plus reached
Yes
No
3635
08
Position actual value <= cam switching
position 1
Yes
No
4025
09
Position actual value <= cam switching
position 2
Yes
No
4025
10
Direct output 1 via traversing block
Yes
No
3616
11
Direct output 2 via traversing block
Yes
No
3616
12
Fixed stop reached
Yes
No
3616,
3617
13
Fixed stop clamping torque reached
Yes
No
3616,
3617
14
Travel to fixed stop active
Yes
No
3616,
3617
r2684.0...15
CO/BO: EPOS status word 2 / POS_ZSW2
CU250D-2_PN_F
CU250D-2_DP_F
Access level:
1
Calculated:
-
Data type:
Unsigned16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
3646
Min Max
Factory
setting
- - -