SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
421
2 Parameters
2.2 List of parameters
Description:
Sets the reference serial number for the memory card.
Using this parameter, if a Control Unit and/or a memory card is replaced at the end customer, the OEM can again
adapt the project to the modified hardware.
Dependency:
Refer to: p7765, p7766, p7767, p7768
Note:
KHP: Know-How Protection
- the OEM may only change this parameter for the use case "Sending encrypted SINAMICS data".
- SINAMICS only evaluates this parameter when powering up from the encrypted "Load into file system..." output or
when powering up from the encrypted PS files. The evaluation is only made when know-how protection and memory
card copy protection have been activated.
Description:
Setting to backup/import/delete NVRAM data.
NVRAM data are non-volatile data in the device (e.g. fault buffer).
For NVRAM data actions, the following data are excluded:
- Crash diagnostics
- CU operating hours counter
- CU temperature
- safety logbook
Value:
0:
Inactive
1:
NVRAM data backup to memory card
2:
Import NVRAM data from the memory card
3:
Delete NVRAM data in the device
10:
Error when clearing
11:
Error when backing up, memory card not available
12:
Error when backing up, insufficient memory space
13:
Error when backing up
14:
Error when importing, memory card not available
15:
Error when importing, checksum error
16:
Error when importing, no NVRAM data available
17:
Error when importing
Notice:
For value = 2, 3:
These actions are only possible when pulses are inhibited.
Note:
After the action has been successfully completed, the parameter is automatically set to zero.
The actions importing and deleting NVRAM data immediately initiate a warm restart.
If the procedure was not successfully completed, then an appropriate fault value is displayed (p7775 >= 10).
Description:
Displays the actual serial number of the Power Module.
The individual characters of the serial number are displayed in the ASCII code in the indices.
p7769[0...20]
KHP memory card reference serial number / KHP mem ref ser_no
Access level:
3
Calculated:
-
Data type:
Unsigned8
Can be changed:
T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -
p7775
NVRAM data backup/import/delete / NVRAM backup
Access level:
3
Calculated:
-
Data type:
Integer16
Can be changed:
C, U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 17
0
r7841[0...15]
Power Module serial number / PM serial no.
Access level:
4
Calculated:
-
Data type:
Unsigned8
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
- - -