background image

Components

900-0156-01-00 Rev B.vsd\Page-1\2013-06-14

©2013 OutBack Power Technologies.  All Rights Reserved.

Contact Technical Support:

Telephone:

+1.360.618.4363

Email:  

[email protected]

Website:  

www.outbackpower.com

Radian System Products 

Major Components

GS7048E Inverter/Charger

GSLC175-AC-230

GS Load Center

GSLC175-AC-230

Inverter/Charger

GS7048E

IMPORTANT:  

Not intended for use with 

life support equipment.

PV and Grid-Tied 

Inverter

Battery Bank

Vented Battery Enclosure

MATE3 

System 

Display and 

Controller

GS Load Center 

(GSLC)

System Display  

MATE3 

MATE3 uses FW-MB3 mounting bracket
MATE3 requires revision 002.015.xxx or higher

Includes Remote Temperature Sensor (RTS)

Optional OutBack Components

FLEXnet DC Monitor

(FN-DC)

Communications 

Manager 

HUB10.3
HUB10
HUB4

AC Sources

Utility Grid (required)
AC Generator (optional)

Main Electrical Panel 
Electrical Distribution Subpanel 

(Protected Load Panel)

Battery Bank

Photovoltaic (PV) Array 

Customer-Supplied Components

Grid-Tied Inverter, 230 Vac

De-energize/Shutdown Procedures

2a

2b

1

2

1

1b

1c 1d

3a

To de-energize or shut down the AC-coupled system:

1.

Turn off (open) the AC circuit breakers. 

2.

Turn off (open) the DC circuit breakers for the battery.  
Wait 5 minutes for the inverter to internally discharge itself. 

3.

Verify 0 Vdc on the first DC bus of the inverter by placing the voltmeter leads 
on         and         .

4.

Verify 0 Vdc on the second DC bus by placing the voltmeter leads on

and        .

5.

Verify 0 Vac on the AC output circuit breakers by placing the voltmeter leads 
on 

and       .  

6.

Verify 0 Vac on the grid-tied inverter terminals        and         .

1

2

Functional Test Points

Battery Voltage Test Points

AC OUT Voltage Test Points 

(Terminal bus bar = TBB)

1a

1b

1c

1d

3a

2b

2a

2b

Grid-Tie Inverter Test Points

WARNING:  Lethal Voltage

Review the system configuration to identify all possible 
sources of energy.  Ensure ALL sources of power are 
disconnected before performing any installation or 
maintenance on this equipment.  Confirm that the 
terminals are de-energized using a validated voltmeter 
(rated for a minimum 1000 Vac and 1000 Vdc) to verify 
the de-energized condition.

WARNING:  Lethal Voltage

The numbered steps will remove power from the 
inverters.  However, sources of energy may still be 
present inside the GSLC and other locations.  To 
ensure absolute safety, disconnect ALL power 
connections at the source.    

WARNING:  Burn Hazard

Internal parts can become hot during 
operation.  Do not remove the cover 
during operation or touch any internal 
parts.  Be sure to allow them 
sufficient time to cool down before 
attempting to perform any product 
maintenance.  

2a

2b

3a

2b

1b

1c

1b

1d

2a

2b

3a

2b

AC-Coupled Application