SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
125
2 Parameters
2.2 List of parameters
Warning:
The maximum voltage difference between analog input terminals AI+, AI-, and the ground must not exceed 35 V.
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (V) of the 2nd value pair of the characteristic.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
The parameters for the characteristic do not have a limiting effect.
p0757[0...1]
CU analog inputs characteristic value x1 / CU AI char x1
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
-50.000 160.000
0.000
p0758[0...1]
CU analog inputs characteristic value y1 / CU AI char y1
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
0.00 [%]
p0759[0...1]
CU analog inputs characteristic value x2 / CU AI char x2
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
-50.000 160.000
10.000
p0760[0...1]
CU analog inputs characteristic value y2 / CU AI char y2
CU240D-2_DP
CU240D-2_PN
CU240D-2_DP_F
CU240D-2_PN_F
Access level:
2
Calculated:
-
Data type:
FloatingPoint32
Can be changed:
U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
9566, 9568, 9576
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
100.00 [%]