background image

 

 

 
 

ibaPADU-8/ -16/ -32/ -32-R 

Manual 

Issue 3.3 

Parallel-Analog-Digital-Converter for 8, 16 or 32 channels 

Summary of Contents for ibaPADU-8

Page 1: ...ibaPADU 8 16 32 32 R Manual Issue 3 3 Parallel Analog Digital Converter for 8 16 or 32 channels ...

Page 2: ...ll compliance is not guaranteed However the information in this publication is updated regularly Required corrections are contained in the following regulations or can be downloaded on the Internet The current version is available for download on our web site http www iba ag com Protection note Windows is a label and registered trademark of the Microsoft Corporation Other pro duct and company name...

Page 3: ...2 Examples for topologies 12 8 Product properties 14 8 1 Properties 14 8 2 Device operating elements and connectors 15 8 2 1 ibaPADU 8 all types 15 8 2 2 ibaPADU 16 ibaPADU 32 ibaPADU 32 R 16 8 2 3 Run link and error LED indicators 18 8 2 4 Analog and digital connector pinning 18 8 2 5 Service interface X12 19 8 2 6 Shield connector s for physical earth 19 8 3 Devices for different analog input ph...

Page 4: ...ettings in ibaPDA V6 25 10 Technical data 27 10 1 Main data or all Device types 27 10 2 Analog inputs 28 10 3 Binary inputs 29 10 4 Device data 29 10 5 Dimensions drawing ibaPADU 8 30 10 6 Dimensions drawing ibaPADU 16 31 10 7 Dimensions drawing ibaPADU 32 32 10 8 Dimensions drawing ibaPADU 32 R 33 11 Support and Contact 34 ...

Page 5: ...regarded to as professional if he she is capable of assessing safety and recognizing possible consequences and risks on the basis of his her spe cialist training knowledge and experience and knowledge of the standard regulations 1 2 Notations In this manual the following notations are used Action Notation Menu command Menu Logic diagram Call of menu command Step 1 Step 2 Step 3 Step x Example Sele...

Page 6: ...process and the system or machine to be controlled there is a risk of death or severe injury The non observance of this safety information may result in a potential risk of death or severe injury The non observance of this safety information may result in a potential risk of injury or material damage Note A note specifies special requirements or actions to be observed Important note Note if some s...

Page 7: ... D channels ibaPADU 32 R 19 rack mount device with 32 A 32 D channels and AC 115 V 250 V power supply If no special reference to a device is made in the following text the devices are named as ibaPADU in general For special measuring tasks devices with different I O physics i e 20 mA or higher input impedance ibaPADU 8 HI are available see chapter 8 3 The devices are ideally suited for the followi...

Page 8: ... The following safety instructions apply particularly to the devices ibaPADU 16 and ibaPADU 32 32R In order to avoid the risk of electrical shock disconnect the power cord or switch off the power supply before installation or dismantling of the device In order to avoid the risk of electrical shock prevent the devices from contact with wa ter The 3 wire power cord must be connected to a correctly g...

Page 9: ...1000 ibaFOB io or ibaFOB 4i ibaFOB io S or ibaFOB 4i S ibaFOB 4i X 2i X 2io X or io X not for ibaPADU devices with S N 1000 ibaFOB 4i D 2i D 2io D or io D Laptop computer with ibaCom PCMCIA F copper based RS485 interface or optic transmission via ibaFO A adaptor PLC system with ibaLink SM 64 IO input ibaLink SM 128V i 2o input 5 2 Software For data acquisition recording or process control you ll n...

Page 10: ...th this action the device should free itself from the DIN rail 6 2 ibaPADU 32 R 6 2 1 Mounting Fix the device with the four front panel screws into the cubicle In case of high me chanical duty acceleration 1 g support the device at the rear end or mount it on rails Once fixed on the rear side connect the power supply cord and switch on the device Connect fiber optic cable s to the TX RX ports and ...

Page 11: ...es which hold 16 A 16 D channels need two addresses an ibaPADU 32 needs four addresses re spectively Hence you may connect chains of 8 ibaPADU 8 or 4 ibaPADU 16 or 2 ibaPADU 32 with 1 fiber optic link It is permitted to combine different ibaPADU devices in one chain Note Cascading ibaPADU 16 ibaPADU 32 or ibaPADU 32 R is allowed with serial num bers 1000 or higher of these devices 3Mbit telegram i...

Page 12: ...e principle of the data pack ages in an ibaFOB telegram Each box contains 8 analog 8 digital signals The device address determines where the data are placed in the te legram Therefore the posi tion of a device in the chain is independent of the address setting Figure 1 Homogenous ibaPADU 8 chain Example 2 ibaPADU 32 chain 1 occupies 1 2 3 and 4 5 occupies 5 6 7 and 8 2 devices in a line structure ...

Page 13: ...overwriting the data from ibaPADU 16 Figure 3 Mixed chain with ibaPADU 16 and ibaPADU 32 Example 4 Connection to Notebooks via ibaCom PCMCIA F card 4 occupies 4 and 5 1 occupies 1 2 3 and4 2 devices in a line structure connected to a notebook computer via ibaCom PCMCIA F card The last device in the chain is connected to the ibaCom PCMCIA F card via the RJ11 cable Use the fiber optic adapter ibaCom...

Page 14: ...and 32 is 1000 Hz Sampling rate for ibaPADU 16 32 of version A2 or higher can be set to 800 Hz or 960 Hz this contributes to operation in a 60 Hz mains environment For ibaPADU 8 only in externally synchronized operation mode and together with ibaFOB io or ibaFOB 4i ibaFOB 4o in ring topology sampling rate can be changed by program ibaLogic in steps of 100 μs between 1 0 ms and 9 9 ms ibaPADU 8 16 ...

Page 15: ...Address switch S1 Mode switch S2 Analog inputs 00 07 X1 Digital input status LEDs L4 L11 Digital inputs 00 07 X5 Top view Serial number and E Mail address Bottom view Service interface 9 pin D Sub X12 RJ11 laptop connector jack X9 Shield connector X29 Figure 5 Device operating elements and connectors 8 2 1 1 Power supply connector X14 A non stabilized DC voltage between 18 V and 32 V is to be conn...

Page 16: ...data for the time period of the interruption 8 2 1 3 Device address setting with Addr switch S1 S1 is used to set the device address 1 8 Each address represents 8 A 8 D chan nels Important note The position of the address switch S1 must not be 0 since otherwise the link is broken 8 2 1 4 Device Mode setting with mode switch S0 S0 sets the device mode Mode 0 Run standard other modes are not support...

Page 17: ...a chain on one FO link when using ibaPADU 32 up to 2 devices 8 2 2 3 Device mode setting with mode switch S0 The switch S0 sets the device mode Switch S0 Mode Meaning 0 Standard sampling rate 1000 Hz 1 ms sample time 14 bit 1 4 times oversampling sampling rate 1000 Hz 1 ms 16 bit 6 Sampling rate 800 Hz for operation in 60 Hz mains environment 14 bit for ibaPADU 16 32 32R version A2 and higher 7 Sa...

Page 18: ... Pin Connector X1 X2 X3 X4 X5 X6 X7 X8 1 AI 00 AI 08 AI 16 AI 24 DI 00 DI 08 DI 16 DI 24 2 AI 00 AI 08 AI 16 AI 24 DI 00 DI 08 DI 16 DI 24 3 AI 01 AI 09 AI 17 AI 25 DI 01 DI 09 DI 17 DI 25 4 AI 01 AI 09 AI 17 AI 25 DI 01 DI 09 DI 17 DI 25 5 AI 02 AI 10 AI 18 AI 26 DI 02 DI 10 DI 18 DI 26 6 AI 02 AI 10 AI 18 AI 26 DI 02 DI 10 DI 18 DI 26 7 AI 03 AI 11 AI 19 AI 27 DI 03 DI 11 DI 19 DI 27 8 AI 03 AI ...

Page 19: ...ote In normal operation mode the V 24 cable must not be connected 8 2 6 Shield connector s for physical earth Proper connection of cable shielding to the device should be ensured The shield con nector can be found on the bottom side of the device or on the right side of each con nector on ibaPADU 16 32 32 R It should be connected with any total shield that serves for all cables In addition each in...

Page 20: ...kΩ RON device is on and ROFF 50 kΩ Derivatives with inputs of up to 60 V are available also in request see chapter Techni cal data 8 3 3 ibaPADU 8 High Impedance 8 analog inputs with 10 V voltage inputs and RON 1 MΩ ROFF 500 kΩ There are devices also available for up to 60 V and with low pass filter see chapter Technical data Figure 8 Simplified input circuitry of the 10V input with ibaPADU HI res...

Page 21: ...n and ROFF 50 kΩ Low pass filter 250 Hz 12 dB Figure 9 Simplified input circuitry of ibaPADU 8 F1 250 Hz 12 dB 8 3 5 ibaPADU 8 I 8 analog inputs with 20 mA RI 50 Ω for current based signals Figure 10 Simplified input circuitry of ibaPADU 8 I 20 mA There are devices also available for currents up to 50 mA see chapter Technical data ...

Page 22: ...pling rate for all devices is 1 Hz The sampling rate for ibaPADU 8 only may be changed for the devices within one ring topology between 1 0 ms and 9 9 ms in steps of 100 μs with ibaLogic and ibaFOB io or ibaFOB 4i ibaFOB 4o or their successors except ibaFOB D In this case a ring topology is required Figure 11 Ring topology for external synchronization of ibaPADU 8 devices ...

Page 23: ...on is better than 2 μs between any device and any chain This mode is only available with ibaLogic and ibaPADU 8 Only ibaLogic is able to ad dress the ibaFOB output mod ule Special device settings for the devices are not necessary Figure 12 Externally synchronized operation of multiple ibaPADU 8 chains Tip All optical signals may be multiplied with an ibaBM FOX i 3o device at any position within th...

Page 24: ...ibaPADU 8 HI F ibaPADU 8 F1 F ibaPADU 8 I F ibaPADU 16 F ibaPADU 32 F ibaPADU 32 R F ibaPADU 8 ICP 1 M ibaPADU 8 M 1 M ibaPADU16 M 1 F M ibaDIG40 1 F M 1 There are separate manuals about these devices 2 F Mode up to 1 kHz 3Mbit data telegram M Mode up to 25 kHz 5Mbit data tele gram Table 2 Accessing data of ibaPADU devices by software Other documentation For more information about the configuratio...

Page 25: ... an ibaPADU 8 16 or 32 module to the corresponding FOB F PCI data interface Figure 13 I O Manager hardware 9 2 1 2 ibaPDA diagnostics check of settings The correct function of the ibaFOB and or ibaPADU may be checked already in the I O manager The interface card is automatically detected by the ibaPDA system By means of the automatic detection function Autodetect the system detects the periph eral...

Page 26: ...l the view provides an overview about the communication parame ters of all FO links A permanent change in Baud rate indicates that no telegram is received This is either due to a missing or faulty fiber optic cable connection or to the fact that the voltage sup ply is not available for the device connected to the board You get further information about the con nected devices when you click on the ...

Page 27: ...Hz axis all ibaPADU 8 types ibaPadu 32 R 2 g with ad ditional rear holder only EMI test parameters EN 55011 Class A EN 61000 4 6 Class 3 EN 61000 4 3 ENV 50204 Class 3 Operating temperature 32 F to 122 F 0 C to 50 C Storage temperature 13 F to 158 F 25 C to 70 C transport temperature 13 F to 158 F 25 C to 70 C Cooling Self cooling Humidity Class F no condensation Protection Class IP20 Length of fi...

Page 28: ...R HI 60 10 2 Analog inputs Number 8 8 8 16 32 Resolution 14 bit Dynamics 80 dB 0 Hz to 500 Hz Frequency response Low pass filter 250 Hz 12 dB 8 F1 8 HI F1 Low pass filter 250 Hz 12 dB 16 F1 Input level type 10 V 8 8 F1 1 V 8 1 10 V HI HI F1 15 V HI 15 24 V HI 24 25 V HI 25 60 V HI 60 20 mA I 50 mA I 50 10 V 10 V 32 32 HI 32 R 60 V 32 HI 60 32 R HI 60 Input impedance Ron 100 kΩ Roff 50 kΩ Ron 1 MΩ ...

Page 29: ...gital ground 1 5 kV 10 4 Device data Montage DIN rail snap in mount Table device 19 rack mount Power supply DC 24 V 20 not stabilized AC 115 V 250 V 50 60 Hz Power Current con sumption no load Typ 300 mA max 400 mA IOFF ON approx 1A Approx 16 W Approx 20 W FO cable Coupling 62 5 125 µm ST Lean Dimension w x h x d 2 1 in x 7 6 in x 6 1 in 54 mm x 194 mm x 155 mm 15 2 x 2 2 x 10 2 385 x 55 x 260 15 ...

Page 30: ...Manual ibaPADU 8 16 32 32 R 30 Issue 3 3 10 5 Dimensions drawing ibaPADU 8 Dimensions given in mm Figure 15 Dimensions drawing ibaPADU 8 ...

Page 31: ...ibaPADU 8 16 32 32 R Manual Issue 3 3 31 10 6 Dimensions drawing ibaPADU 16 Dimensions given in mm Figure 16 Dimensions drawing ibaPADU 16 ...

Page 32: ...Manual ibaPADU 8 16 32 32 R 32 Issue 3 3 10 7 Dimensions drawing ibaPADU 32 Dimensions given in mm Figure 17 Dimensions drawing ibaPADU 32 ...

Page 33: ...ibaPADU 8 16 32 32 R Manual Issue 3 3 33 10 8 Dimensions drawing ibaPADU 32 R Dimensions given in mm Figure 18 Dimensions drawing ibaPADU 32 R ...

Page 34: ...u require support specify the serial number iba S N of the product Contact Headquarters iba AG Koenigswarterstr 44 90762 Fuerth Germany Phone 49 911 97282 0 Fax 49 911 97282 33 E Mail iba iba ag com Contact Mr Harald Opel Regional and Worldwide For contact data of your regional iba office or representative please refer to our web site www iba ag com ...

Reviews: