If the chiller is equipped with an air filter, the filter has to be changed/cleaned monthly, or, if required in a shorter time
interval
Inspect the condenser monthly on the external side to see if it is clean.
The fins of the condenser must not have any dust
deposits or residual products or sludges on their surface .
The condenser must be cleaned in monthly intervals, or, if required in shorter time intervals.
If the Chiller is equipped with a filter on the hydraulical side (filter to be installed in the inlet of the chiller), the filter has to be
checked/cleaned monthly, or if required, in a shorter time interval
It’s recommended to change the water glycole mixture 20% every year (every 2 years if it’s a 30 % glycole mixture) to allow
the operation of the unit in the best conditions.
Longer standstill of the chiller requires draining of the tank and complete water circuit. Open the ball valve at the end of the
draining hose to drain the circuit. When the drain operation is finished close again the ball valve, otherwise when you refill
again the circuit water will automatically darined again from the hose.
For a new installation, it is recommended to empty the hydraulic circuit. Please, refer to chapter
4
for the lifting of the unit
and chapters
7
and
11
for connection and start up.
It is recommended to check safety discharge valve every 24/36 months. Leakages and/or visible scale may suggest
potential malfunction.
Please note: it is necessary to replace safety discharge valve after its intervention. Safety discharge pressure set is not
guaranteed after first intervention
Refrigeration circuit is subjected to high stationary and operating pressures.
Air filter
Picture 24
– Air filter
placement
Picture 25
– Condenser external surface
Summary of Contents for EB 130 WT
Page 20: ...English 20 APPENDIX A1...
Page 21: ...English 21 APPENDIX A2...
Page 26: ...English 26 Max pressure valve Thermostatic Valve Evaporator Refrigerant pipes Fan Pump...
Page 54: ...Deutsch 54 ANLAGE A1...
Page 56: ...Deutsch 56 ANLAGE A2...
Page 62: ...Deutsch 62 H chstdruckventil Thermostatisches Ventil Verdampfer K hlmittelrohre L fter Pumpe...
Page 89: ...Italiano 89 ALLEGATO A1...
Page 91: ...Italiano 91 ALLEGATO A2...
Page 124: ...Espa ol 124 ANEXO A1...
Page 126: ...Espa ol 126 ANEXO A2...
Page 159: ...Fran ais 159 ANNEXE A1...
Page 161: ...Fran ais 161 ANNEXE A2...
Page 177: ...177 1 2 3 4 5 6 7 8 8 1 9 10 11 12 A1 A2 B1 B2 C 1 2 D 1 12 2 EN 60204...
Page 178: ...178 30 435 PSI 5 8 85 PSI PWW PS 12...
Page 182: ...182 4 7 3...
Page 183: ...183 3 b PWW 3 4 PWW 9000 12000 1 PWW 18000 24000 3 4 PWW 9000 12000 1 PWW 18000 24000 4...
Page 187: ...187 60 90 m PFANNENBERG 18 15 ISO 4406 10 40 C 45 C 50 C 15 C PFANNENBERG 0 C 11 A1 A2 PWW A2...
Page 189: ...189 11 12 13 14...
Page 190: ...190 l R S T 15 16 17...
Page 191: ...191 5 R S T 18 19 20 21...
Page 192: ...192 PFANNENBERG...
Page 193: ...193 12 KLIXON 2 1 Klixon...
Page 194: ...194 40 C...
Page 195: ...195...
Page 196: ...196 A1...
Page 198: ...198 A2...
Page 200: ...200 B1 n 842 2006 2 PWW 22 23...
Page 201: ...201 A2 20 30 5 7 11 24 25...
Page 202: ...202 24 36 25 309 1 2004...
Page 203: ...203 B2 EB EB150 T EB190 WT...
Page 204: ...204...
Page 205: ...205 C 1 Pfannenberg PFANNENBERG 1 2 3 26 2 1 0...
Page 210: ...210 2 PWW INLET 2 1 31 PWW Air purge valve Max safety valve Refill valve...
Page 211: ...211 D 1 1 1 90 m pH 1 2 3 4 32...