Corrosion protection:
PFANNENBERG recommends that Glycol is also used as a rust inhibitor. The minimum percentage of glycol (in a mixture with
water) recommended by some important glycol supplier (Clariant, Total, Dowfrost, etc..) is
between 20% and 30%.
CAUTION:
Please contact the glycol supplier to know the minimum percentage needed in order to use
the glycol as rust inhibitor
CAUTION:
All the typelabel of the STD Pfannenberg unit are provided with a percentage of glycol of
20%
The percentages of glycol into the mixture is related to the minimum working temperature of the mixture (that must be in line
with the minimum working set point of the unit, please see the technical data of the unit):
Propylene glycol
dilution
Working range temperature
Freezing point
%
Min [°C]
Max [°C]
PP20P
20
+10
+101
-8
PP30P
30
0
+103
-14
PP50P
54
-25
+104
-38
Ethylene glycol
dilution
Working range temperature
Freezing point
%
Min [°C]
Max [°C]
PP20E
20
+10
+102
-8
PP30E
30
0
+103
-15
PP50E
50
-25
+108
-38
CAUTION:
The higher the concentration of glycol the lower the amount of heat rejection you will be
able to get out of the fluid.
CAUTION:
The type of glycol (propylene or ethylene) must be in conformity with the Standard
requested by the application, please contact the Glycol supplier
.
8.1 Waterquality
To keep the hydraulic circuit correct and trouble-free, it is necessary, to check the water quality and if necessary, carry out water
treatment. The standard circuit of a water chiller is a half open system, that means, part of the water steams/evaporates out
during operation. That means, that the concentration of chloride is getting higher and the system water will cause corrosion on
the installed components.
Summary of Contents for EB 130 WT
Page 20: ...English 20 APPENDIX A1...
Page 21: ...English 21 APPENDIX A2...
Page 26: ...English 26 Max pressure valve Thermostatic Valve Evaporator Refrigerant pipes Fan Pump...
Page 54: ...Deutsch 54 ANLAGE A1...
Page 56: ...Deutsch 56 ANLAGE A2...
Page 62: ...Deutsch 62 H chstdruckventil Thermostatisches Ventil Verdampfer K hlmittelrohre L fter Pumpe...
Page 89: ...Italiano 89 ALLEGATO A1...
Page 91: ...Italiano 91 ALLEGATO A2...
Page 124: ...Espa ol 124 ANEXO A1...
Page 126: ...Espa ol 126 ANEXO A2...
Page 159: ...Fran ais 159 ANNEXE A1...
Page 161: ...Fran ais 161 ANNEXE A2...
Page 177: ...177 1 2 3 4 5 6 7 8 8 1 9 10 11 12 A1 A2 B1 B2 C 1 2 D 1 12 2 EN 60204...
Page 178: ...178 30 435 PSI 5 8 85 PSI PWW PS 12...
Page 182: ...182 4 7 3...
Page 183: ...183 3 b PWW 3 4 PWW 9000 12000 1 PWW 18000 24000 3 4 PWW 9000 12000 1 PWW 18000 24000 4...
Page 187: ...187 60 90 m PFANNENBERG 18 15 ISO 4406 10 40 C 45 C 50 C 15 C PFANNENBERG 0 C 11 A1 A2 PWW A2...
Page 189: ...189 11 12 13 14...
Page 190: ...190 l R S T 15 16 17...
Page 191: ...191 5 R S T 18 19 20 21...
Page 192: ...192 PFANNENBERG...
Page 193: ...193 12 KLIXON 2 1 Klixon...
Page 194: ...194 40 C...
Page 195: ...195...
Page 196: ...196 A1...
Page 198: ...198 A2...
Page 200: ...200 B1 n 842 2006 2 PWW 22 23...
Page 201: ...201 A2 20 30 5 7 11 24 25...
Page 202: ...202 24 36 25 309 1 2004...
Page 203: ...203 B2 EB EB150 T EB190 WT...
Page 204: ...204...
Page 205: ...205 C 1 Pfannenberg PFANNENBERG 1 2 3 26 2 1 0...
Page 210: ...210 2 PWW INLET 2 1 31 PWW Air purge valve Max safety valve Refill valve...
Page 211: ...211 D 1 1 1 90 m pH 1 2 3 4 32...