Debug Table
The information described below are useful for the service staff.
The faults that require the intervention of a refrigeration
engineer must be carried out only by specialized staff. Follow all electrical legislation when working on the unit based on valid
laws of the countries were the unit is placed.
Chiller
Problem
Cause
Possible corrective Action
The unit does not start
up
No supply voltage
Check the supply main voltage line
Not working thermostat
Inspect the connection, check and correct the parameter settings and if there
is no fault, replace the thermostat,
The compressor protector (KLIXON)
has switched off
Important:
After the shut down of the compressor, the resetting time will
depending on the environment of the compressor: In a hot closed
environment it will be 2 hours, in ventilated 1 hour.
Note:
The compressors are protected against high temperatures and
currents, with of an internal or external device (Klixon). The internal/external
device protects the compressor against the following situations:
overheating due to an inadequate cooling of the compressor motor.
Blocked compressor due to a high temperature of the motor or a high
current.
Loose connections which may cause high currents
It works, but does not
cool
There is not enough gas in the
equipment
Service by a refrigeration engineer
Faulty thermostatic valve
Service by a refrigeration engineer
Too high heat load
Possible wrong application, to be checked with our staff
Refrigerant Cycle is not working
Problem
Cause
Possible corrective Action
Switching of low
pressure switch
The unit works for short periods, it
stops and starts again after a while.
The causes are:
Low gas level in the equipment
Outlet line of the compressor is
blocked and more in detail:
satured dehydrating filter,
blocked thermostatic valve.
Service by a refrigeration engineer
Switching of the high
pressure switch
The unit does not work.
The causes are:
Dirty condenser
Clean the condenser with compressed air if it is full of dust, or use proper
solvents suitable to remove sludges.
Summary of Contents for EB 130 WT
Page 20: ...English 20 APPENDIX A1...
Page 21: ...English 21 APPENDIX A2...
Page 26: ...English 26 Max pressure valve Thermostatic Valve Evaporator Refrigerant pipes Fan Pump...
Page 54: ...Deutsch 54 ANLAGE A1...
Page 56: ...Deutsch 56 ANLAGE A2...
Page 62: ...Deutsch 62 H chstdruckventil Thermostatisches Ventil Verdampfer K hlmittelrohre L fter Pumpe...
Page 89: ...Italiano 89 ALLEGATO A1...
Page 91: ...Italiano 91 ALLEGATO A2...
Page 124: ...Espa ol 124 ANEXO A1...
Page 126: ...Espa ol 126 ANEXO A2...
Page 159: ...Fran ais 159 ANNEXE A1...
Page 161: ...Fran ais 161 ANNEXE A2...
Page 177: ...177 1 2 3 4 5 6 7 8 8 1 9 10 11 12 A1 A2 B1 B2 C 1 2 D 1 12 2 EN 60204...
Page 178: ...178 30 435 PSI 5 8 85 PSI PWW PS 12...
Page 182: ...182 4 7 3...
Page 183: ...183 3 b PWW 3 4 PWW 9000 12000 1 PWW 18000 24000 3 4 PWW 9000 12000 1 PWW 18000 24000 4...
Page 187: ...187 60 90 m PFANNENBERG 18 15 ISO 4406 10 40 C 45 C 50 C 15 C PFANNENBERG 0 C 11 A1 A2 PWW A2...
Page 189: ...189 11 12 13 14...
Page 190: ...190 l R S T 15 16 17...
Page 191: ...191 5 R S T 18 19 20 21...
Page 192: ...192 PFANNENBERG...
Page 193: ...193 12 KLIXON 2 1 Klixon...
Page 194: ...194 40 C...
Page 195: ...195...
Page 196: ...196 A1...
Page 198: ...198 A2...
Page 200: ...200 B1 n 842 2006 2 PWW 22 23...
Page 201: ...201 A2 20 30 5 7 11 24 25...
Page 202: ...202 24 36 25 309 1 2004...
Page 203: ...203 B2 EB EB150 T EB190 WT...
Page 204: ...204...
Page 205: ...205 C 1 Pfannenberg PFANNENBERG 1 2 3 26 2 1 0...
Page 210: ...210 2 PWW INLET 2 1 31 PWW Air purge valve Max safety valve Refill valve...
Page 211: ...211 D 1 1 1 90 m pH 1 2 3 4 32...