D-208
Parameter Reference
AC30 series Variable Speed Drive
PNO Name
Path
Type
Default
Range
Units
WQ
View
Notes MBus
0563 PMAC Torque Const KT
Same as PNO 555
REAL
1.00
0.00 to 10000.00
Nm/A ALWAYS TECHNICIAN 6
01653
0564 PMAC Motor Inertia
Same as PNO 555
REAL
0.00100
0.00000 to 100.00000
kgm²
ALWAYS TECHNICIAN 6
01655
0565 PMAC Therm Time Const
Same as PNO 555
TIME
62.000
0.000 to 10000.000
s
ALWAYS TECHNICIAN 6
01657
0568 Magnetising Current
Parameters::Motor Control::Induction Motor Data
REAL
1.00
0.00 to 10000.00
A
ALWAYS ENGINEER
6
01663
0569 Rotor Time Constant
Parameters::Motor Control::Induction Motor Data
TIME
0.100
0.005 to 100.000
s
ALWAYS ENGINEER
6
01665
0570 Leakage Inductance
Parameters::Motor Control::Induction Motor Data
REAL
1.000
0.000 to 1000.000
mH
ALWAYS ENGINEER
6
01667
0571 Stator Resistance
Parameters::Motor Control::Induction Motor Data
REAL
0.0000
0.0000 to 100.0000
Ohm
ALWAYS ENGINEER
6
01669
0572 Mutual Inductance
Parameters::Motor Control::Induction Motor Data
REAL
100.00
0.00 to 10000.00
mH
ALWAYS ENGINEER
6
01671
0591 Local
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN
01709
0592 Local Reference
Parameters::Motor Control::Sequencing
REAL
0.00
0.00 to 100.00
%
ALWAYS OPERATOR
01711
0610 App Control Word
Parameters::Motor Control::Sequencing
WORD
(bitfield)
0000
0:SWITCH ON
1:ENABLE VOLTAGE
2:NOT QUICKSTOP
3:ENABLE OPERATION
7:RESET FAULT
8:EXTERNAL FAULT
12:USE JOG REFERENCE
13:REVERSE DIRECTION
14:AUTO INITIALISE
15:EVENT TRIGGERED OP
ALWAYS ENGINEER
2
01747
0611 App Control Word.SWITCH ON
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS ENGINEER
2
01749
0612 App Control Word.ENABLE VOLTAGE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS ENGINEER
2
01751
0613 App Control Word.NOT QUICKSTOP
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS ENGINEER
2
01753
0614 App Control Word.ENABLE OPERATION
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS ENGINEER
2
01755
0618 App Control Word.RESET FAULT
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS ENGINEER
2
01763
0619 App Control Word.EXTERNAL FAULT
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS ENGINEER
2
01765
0623 App Control Word.USE JOG REFERENCE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS ENGINEER
2
01773
0624 App Control Word.REVERSE DIRECTION
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS ENGINEER
2
01775
0625 App Control Word.AUTO INITIALISE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS ENGINEER
2
01777
0626 App Control Word.EVENT TRIGGERED OP
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS ENGINEER
2
01779
0627 Comms Control Word
Parameters::Motor Control::Sequencing
WORD
(bitfield)
0000
0:SWITCH ON
1:ENABLE VOLTAGE
2:NOT QUICKSTOP
3:ENABLE OPERATION
7:RESET FAULT
8:EXTERNAL FAULT
10:USE COMMS CONTROL
11:USE COMMS REFERENCE
12:USE JOG REFERENCE
13:REVERSE DIRECTION
14:AUTO INITIALISE
15:EVENT TRIGGERED OP
ALWAYS TECHNICIAN 2
01781
0628 Comms Control Word.SWITCH ON
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01783
0629 Comms Control Word.ENABLE VOLTAGE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01785
0630 Comms Control Word.NOT QUICKSTOP
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01787
0631 Comms Control Word.ENABLE OPERATION
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01789
0635 Comms Control Word.RESET FAULT
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01797
0636 Comms Control Word.EXTERNAL FAULT
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01799
0638 Comms Control Word.USE COMMS CONTROL
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01803
0639 Comms Control Word.USE COMMS REFERENCE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01805
0640 Comms Control Word.USE JOG REFERENCE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01807
0641 Comms Control Word.REVERSE DIRECTION
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01809
0642 Comms Control Word.AUTO INITIALISE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01811
0643 Comms Control Word.EVENT TRIGGERED OP
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS TECHNICIAN 2
01813
0644 Control Word
Parameters::Motor Control::Sequencing
WORD
(bitfield)
0:SWITCH ON
1:ENABLE VOLTAGE
2:NOT QUICKSTOP
3:ENABLE OPERATION
7:RESET FAULT
8:EXTERNAL FAULT
10:USE COMMS CONTROL
11:USE COMMS REFERENCE
12:USE JOG REFERENCE
13:REVERSE DIRECTION
14:AUTO INITIALISE
15:EVENT TRIGGERED OP
NEVER
TECHNICIAN
01815
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...