4-21
Installation
AC30 series Variable Speed Inverter
AC30V CONTROL WIRING CONNECTIONS
Terminal ID
Function
X10/01
STO A Input
X10/02
STO Common
X10/03
STO B Input
X10/04
STO Common
X10/05
STO Status A
X10/06
STO Status B
X11/01
ANIN 01
(+10V, 0-10V, 0-20mA, 4-20mA)
X11/02
ANIN 02
(+10V, 0-10V)
X11/03
ANOUT 01 (+10V, 0-10V)
X11/04
ANOUT 02 (0-10V, 0-20mA, 4-20mA)
X11/05
+10V reference
X11/06
-10V reference
X12/01 (LH)
DIGIN 04 / DIGOUT 01
X12/02
DIGIN 05 / DIGOUT 02
X12/03
DIGIN 06 / DIGOUT 03
X12/04
DIGIN 07 / DIGOUT 04
X12/05
User +24V output
X12/06
0V
X13/01 (LH)
0V
X13/02
DIGIN 1
X13/03
DIGIN 2
X13/04
DIGIN 3
X13/05
+24V AUX input
– AC30V and AC30P only
X13/06
0V AUX input
– AC30V and AC30P only
X14/01 (BOT)
Relay 01 (contact A)
– AC30V only
X14/02
Relay 01 (contact B)
– AC30V only
X14/03
Relay 02 (contact A)
– AC30V only
X14/04
Relay 02 (contact B)
– AC30V only
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...