![Parker AC30 series User Manual Download Page 464](http://html2.mh-extra.com/html/parker/ac30-series/ac30-series_user-manual_3745313464.webp)
D-204
Parameter Reference
AC30 series Variable Speed Drive
PNO Name
Path
Type
Default
Range
Units
WQ
View
Notes MBus
0257 Autotune Test Disable
Same as PNO 255
WORD
(bitfield)
0000
0:Stator Resistance
1:Leakage Inductance
2:Magnetising Current
3:Rotor Time Constant
4:Encoder Direction
STOPPED TECHNICIAN 6
01041
0258 Autotune Test Disable.Stator Resistance
Same as PNO 255
BOOL
FALSE
STOPPED TECHNICIAN 6
01043
0259 Autotune Test Disable.Leakage Inductance
Same as PNO 255
BOOL
FALSE
STOPPED TECHNICIAN 6
01045
0260 Autotune Test Disable.Magnetising Current
Same as PNO 255
BOOL
FALSE
STOPPED TECHNICIAN 6
01047
0261 Autotune Test Disable.Rotor Time Constant
Same as PNO 255
BOOL
FALSE
STOPPED TECHNICIAN 6
01049
0262 Autotune Test Disable.Encoder Direction
Same as PNO 255
BOOL
FALSE
STOPPED TECHNICIAN 6
01051
0274 Autotune Ramp Time
Same as PNO 255
TIME
10.000
1.000 to 1000.000
s
STOPPED TECHNICIAN 6
01075
0286 MRAS Speed Percent
Parameters::Motor Control::MRAS
REAL
x.xx
Min to Max
%
NEVER
ENGINEER
01099
0287 MRAS Speed RPM
Parameters::Motor Control::MRAS
REAL
x.xx
Min to Max
RPM
NEVER
ENGINEER
01101
0289 MRAS Field Frequency
Parameters::Motor Control::MRAS
REAL
x.xx
Min to Max
Hz
NEVER
ENGINEER
01105
0290 MRAS Torque Percent
Parameters::Motor Control::MRAS
REAL
x.xx
Min to Max
%
NEVER
ENGINEER
01107
0291 MRAS Torque
Parameters::Motor Control::MRAS
REAL
x.xx
Min to Max
Nm
NEVER
ENGINEER
01109
0305 Current Limit
Setup::Motor Control::Control and Type
Parameters::Motor Control::Current Limit
REAL
150.0
0.0 to 300.0
%
ALWAYS TECHNICIAN
01137
0307 Regen Limit Enable
Parameters::Motor Control::Current Limit
BOOL
TRUE
ALWAYS ENGINEER
01141
0310 VHz Flying Start Enable
Parameters::Motor Control::Flycatching
BOOL
FALSE
ALWAYS TECHNICIAN
01147
0311 VC Flying Start Enable
Parameters::Motor Control::Flycatching
BOOL
FALSE
ALWAYS TECHNICIAN
01149
0312 Flying Start Mode
Parameters::Motor Control::Flycatching
USINT
(enum)
0
0:ALWAYS
1:TRIP OR POWER UP
2:TRIP
ALWAYS TECHNICIAN
01151
0313 Search Mode
Parameters::Motor Control::Flycatching
USINT
(enum)
0
0:BIDIRECTIONAL
1:UNIDIRECTION
ALWAYS TECHNICIAN
01153
0314 Search Volts
Parameters::Motor Control::Flycatching
REAL
9.0
0.0 to 100.0
%
ALWAYS TECHNICIAN 6
01155
0315 Search Boost
Parameters::Motor Control::Flycatching
REAL
40.0
0.0 to 50.0
%
ALWAYS TECHNICIAN 6
01157
0316 Search Time
Parameters::Motor Control::Flycatching
TIME
3.000
0.100 to 60.000
s
ALWAYS TECHNICIAN 6
01159
0317 Min Search Speed
Parameters::Motor Control::Flycatching
REAL
5
0 to 500
Hz
ALWAYS TECHNICIAN
01161
0318 Flying Reflux Time
Parameters::Motor Control::Flycatching
TIME
2.000
0.100 to 10.000
s
ALWAYS TECHNICIAN 6
01163
0324 DC Inj Deflux Time
Parameters::Motor Control::Inj Braking
TIME
0.500
0.100 to 20.000
s
ALWAYS TECHNICIAN 6
01175
0325 DC Inj Frequency
Parameters::Motor Control::Inj Braking
REAL
9
1 to 500
Hz
ALWAYS TECHNICIAN 6
01177
0326 DC Inj Current Limit
Parameters::Motor Control::Inj Braking
REAL
100.0
50.0 to 150.0
%
ALWAYS TECHNICIAN 6
01179
0327 DC Pulse Time
Parameters::Motor Control::Inj Braking
TIME
2.000
0.000 to 100.000
s
ALWAYS TECHNICIAN 6
01181
0328 Final DC Pulse Time
Parameters::Motor Control::Inj Braking
TIME
1.000
0.000 to 10.000
s
ALWAYS TECHNICIAN 6
01183
0329 DC Current Level
Parameters::Motor Control::Inj Braking
REAL
3.0
0.0 to 25.0
%
ALWAYS TECHNICIAN 6
01185
0330 DC Inj Timeout
Parameters::Motor Control::Inj Braking
TIME
90.000
0.000 to 600.000
s
ALWAYS TECHNICIAN 6
01187
0331 DC Inj Base Volts
Parameters::Motor Control::Inj Braking
REAL
100.00
0.00 to 115.47
%
ALWAYS TECHNICIAN 6
01189
0332 100% Mot Current
Parameters::Motor Control::Motor Load
REAL
x.x
0.0 to 10000.0
NEVER
TECHNICIAN
01191
0333 Mot Inv Time Overl'd
Parameters::Motor Control::Motor Load
REAL
x.
0 to 500
%
NEVER
TECHNICIAN
01193
0334 Mot Inv Time Delay
Parameters::Motor Control::Motor Load
TIME
60.000
6.000 to 60.000
s
ALWAYS TECHNICIAN
01195
0335 Mot Inv Time Warning
Parameters::Motor Control::Motor Load
BOOL
NEVER
TECHNICIAN
01197
0336 Mot Inv Time Active
Parameters::Motor Control::Motor Load
BOOL
NEVER
TECHNICIAN
01199
0337 Mot Inv Time Output %
Parameters::Motor Control::Motor Load
REAL
x.x
0.0 to 500.0
%
NEVER
TECHNICIAN
01201
0338 Mot I2T TC
Parameters::Motor Control::Motor Load
TIME
0.000 to 1000000.000
s
NEVER
TECHNICIAN
01203
0339 Actual Mot I2T Output
Parameters::Motor Control::Motor Load
REAL
x.x
0.0 to 500.0
%
NEVER
TECHNICIAN
01205
0340 Mot I2T Active
Parameters::Motor Control::Motor Load
BOOL
NEVER
OPERATOR
01207
0341 Mot I2T Warning
Parameters::Motor Control::Motor Load
BOOL
NEVER
TECHNICIAN
01209
0342 Mot I2T Enable
Parameters::Motor Control::Motor Load
BOOL
NEVER
TECHNICIAN
01211
0343 100% Stk Current
Parameters::Motor Control::Stack Inv Time
REAL
x.x
0.0 to 10000.0
A
NEVER
TECHNICIAN
01213
0344 Long Overload Level
Parameters::Motor Control::Stack Inv Time
REAL
x.
0 to 200
%
NEVER
TECHNICIAN
01215
0345 Long Overload Time
Parameters::Motor Control::Stack Inv Time
TIME
0.000 to 100000.000
s
NEVER
TECHNICIAN
01217
0346 Short Overload Level
Parameters::Motor Control::Stack Inv Time
REAL
x.
0 to 200
%
NEVER
TECHNICIAN
01219
0347 Short Overload Time
Parameters::Motor Control::Stack Inv Time
TIME
0.000 to 10000.000
s
NEVER
TECHNICIAN
01221
0348 Inv Time Aiming Point
Parameters::Motor Control::Stack Inv Time
REAL
105.00
0.00 to 125.00
%
ALWAYS TECHNICIAN
01223
0349 Inv Time Output
Parameters::Motor Control::Stack Inv Time
REAL
x.
0 to 500
%
NEVER
TECHNICIAN
01225
0350 Inv Time Up Rate
Parameters::Motor Control::Stack Inv Time
TIME
5.000
0.000 to 120.000
s
STOPPED ENGINEER
01227
0351 Inv Time Down Rate
Parameters::Motor Control::Stack Inv Time
TIME
5.000
0.000 to 120.000
s
STOPPED ENGINEER
01229
0352 Inv Time Warning
Parameters::Motor Control::Stack Inv Time
BOOL
NEVER
TECHNICIAN
01231
0353 Inv Time Active
Parameters::Motor Control::Stack Inv Time
BOOL
NEVER
TECHNICIAN
01233
0354 Slip Compensatn Enable
Parameters::Motor Control::Slip Compensation
BOOL
FALSE
ALWAYS TECHNICIAN
01235
0356 SLP Motoring Limit
Parameters::Motor Control::Slip Compensation
REAL
150
0 to 600
RPM
ALWAYS TECHNICIAN 6
01239
0357 SLP Regen Limit
Parameters::Motor Control::Slip Compensation
REAL
150
0 to 600
RPM
ALWAYS TECHNICIAN 6
01241
0360 Slew Rate Enable
Parameters::Motor Control::Slew Rate
BOOL
TRUE
ALWAYS TECHNICIAN
01247
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...