Sequencing Logic
B-4
AC30 series Variable Speed Inverter
Transition 1: NOT READY TO SWITCH ON to SWITCH ON DISABLED
Automatic transition when initialisation has been completed and application has been loaded.
Transition 2: SWITCH ON DISABLED to READY TO SWITCH ON
Shutdown command received from control device or local signal.
Transition 3: READY TO SWITCH ON to SWITCHED ON
Switch On command received from control device or local signal.
Transition 4: SWITCHED ON to OPERATION ENABLED
Enable Operation (Run Forward, Run Reverse or Jog) command received from control device or local signal.
Transition 5: OPERATION ENABLED to SWITCHED ON
Disable Operation (Stop) command received from control device or local signal and Disabling (Stopping) function completed.
Transition 6: SWITCHED ON to READY TO SWITCH ON
Shutdown command received from control device or local signal.
Transition 7: READY TO SWITCH ON to SWITCH ON DISABLED
Quick Stop or Disable Voltage command received from control device or local signal.
Transition 8: OPERATION ENABLED to READY TO SWITCH ON
Shutdown command received from control device or local signal and Shutdown function completed.
Transition 9: OPERATION ENABLED to SWITCH ON DISABLED
Disable Voltage command received from control device or local signal.
Transition 10: SWITCHED ON to SWITCH ON DISABLED
Disable Voltage or Quick Stop command received from control device or local signal.
Transition 11: OPERATION ENABLED to QUICKSTOP ACTIVE
Quick Stop command received from control device or local signal.
Transition 12: OPERATION ENABLED to QUICKSTOP ACTIVE
Automatic transition when the Quick Stop function is completed or Disable Voltage command received.
Transition 13: any state to FAULT REACTION ACTIVE
Fault (Trip) occurred.
Transition 14: FAULT REACTION ACTIVE to FAULT
Automatic transition when Fault Reaction function completed or Disable Voltage command received.
Transition 15: FAULT to SWITCH ON DISABLED
Fault Reset command received from control device or local signal and there are no active faults.
Summary of Contents for AC30 series
Page 48: ...4 27 Installation AC30 series Variable Speed Inverter Basic Speed Control Wiring...
Page 50: ...4 29 Installation AC30 series Variable Speed Inverter Auto Manual Control Wiring...
Page 52: ...4 31 Installation AC30 series Variable Speed Inverter Raise Lower Trim Wiring...
Page 54: ...4 33 Installation AC30 series Variable Speed Inverter Presets Speeds Wiring...
Page 56: ...4 35 Installation AC30 series Variable Speed Inverter PID Control Wiring...
Page 150: ...9 25 Setup Wizard AC30 series Variable Speed Inverter Figure 9 16 Charting Drive Parameters...
Page 233: ...Compliance C 20 AC30 series Variable Speed Inverter Frame H...
Page 234: ...C 21 Compliance AC30 series Variable Speed Inverter Frame J...
Page 266: ...D 6 Parameter Reference AC30 series Variable Speed Drive...
Page 343: ...Parameter Reference D 83 AC30 series Variable Speed Drive Offset Input 100 100 x Scale Value...
Page 495: ...E Plan Library E 2 AC30 series Variable Speed Inverter Which then brings up the E Plan page...